Page 8

3c. Fan Proving Switch Installation

NOTE:

 If installing the MV2, the fan proving

switch is factory installed. This section does not apply.

Test Port: the fan proving switch on the MV3,

MV4, and MV5 includes a test port which can be used
to measure the pressure in the switch. The black
plastic cap over this test port must be in place during
regular operation of the Mighty Venter.

The fan proving switch installation procedure for

the MV3 is as follows:

1.

Mount the fan proving switch to a flat surface
within 4 feet (1.2m) of the Mighty Venter.

NOTE:

 It is important that the fan proving

switch be mounted in a vertical position.

2.

Connect the ¼" aluminum tubing from the fan
proving switch to the Mighty Venter housing
using provided fittings.

The fan proving switch installation procedure for

the MV4 and MV5  is as follows:

1.

Mount the supplied electrical box to a flat
surface within 4 feet (1.2m) of the Mighty
Venter. 

NOTE:

 It is important that the electrical

box is mounted so that the fan proving switch is
in a vertical position.

2.

Connect the ¼" aluminum tubing from the fan
proving switch to the Mighty Venter housing
using provided fittings.

3d. Wiring

WARNING

All wiring from the Mighty Venter to the appliance
must be in compliance with local codes or in their
absence, the National Electric Code (NFPA #70) in
the United States and the CSA C22.1 Electrical
Code in Canada

a)

Connect the black and white (120 VAC) leads
from the Mighty Venter to the boiler control box.
Connect these leads with wire nuts to the boiler
circuit as shown in Figure 5. 

NOTE:

 If correctly

wired (as shown in Figure 5), the power to the
Mighty Venter will be disconnected if the boiler
toggle switch is turned off.

b)

Connect the red, blue and orange (24 VAC)
wires to the terminal blocks as shown in
Figure 5.

c)

Remove the factory-installed jumper from
between boiler terminals 3 and 4.

Ensure that the current capacities of wires,

switches, etc., at 120 VAC meet the ratings as
indicated in Table 5.

Equivalent

Mighty Venter

Full Load Currents

Model

Motor HP

(Amperes - 120VAC)

MV2

1/8

4.4

MV3

1/4

5.8

MV4

1/3

7.2

MV5

1

16

Table 5. Electrical Ratings.

Содержание MV2

Страница 1: ...nstallation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of...

Страница 2: ...General Information 1a Sizing 3 1b Installer Cautions 3 SECTION 2 Side Wall Vent Hood Location 2a Side Wall Vent Hood Location 4 SECTION 3 Installation 3a Inspection and Unpacking 4 3b Power Venter Mo...

Страница 3: ...1 the National Electric Code NFPA 70 or the Canadian Electrical Code CSA C22 1 and the Occupational Safety and Health Act OSHA 3 Any modifications to the Power Venter motor or wiring may void the warr...

Страница 4: ...peration 17 Ambient temperature surrounding Mighty Venter must not exceed 104 F 40 C 18 To prevent personal injury and equipment damage disconnect power supply to boiler or heater when working on Migh...

Страница 5: ...ludes one Installation Manual specific to the Vent Hood If any items are missing from the package contact Laars Be prepared with your purchase order number and the order number on the shipping documen...

Страница 6: ...nimum equivalent vent pipe length is 11 3 4m Slope Note 9 Supports Note 8 Vent pipe is customer supplied G H F J B Reducer dimensions For all sizes 1 2 3 4 B J Note 7 Clearances to combustibles 6 152m...

Страница 7: ...r 1 4 threaded rod with nuts and washers for mounting see Figure 3 for MV3 see Figure 4 for MV4 and MV5 The Mighty Venter may be mounted in any position as long as the shaft of the motor remains horiz...

Страница 8: ...he electrical box is mounted so that the fan proving switch is in a vertical position 2 Connect the aluminum tubing from the fan proving switch to the Mighty Venter housing using provided fittings 3d...

Страница 9: ...er Junction Box Mighty Venter NOTE The black BK and white W leads from the Mighty Venter to the junction box do not require field wiring on Model MV2 Color Legend BK Black W White R Red Y Yellow BL Bl...

Страница 10: ...LAARS Heating Systems Page 10...

Страница 11: ...Mighty Venter Power Vent Systems Page 11...

Страница 12: ...ville Ontario Canada Return Instructions After faulty component is determined ship inoperative part with proofs of purchase and installation date transportation prepaid directly to one of the addresse...

Отзывы: