LAARS Heating Systems

Page 6

Table 4.

NOTES:

1. The asterisk (*) denotes parts that are

included with the Mighty Venter kit.

2. To calculate the equivalent vent pipe

length, add the straight pipe plus 10 feet
(3.0m) for every 90° elbow and 5 feet
(1.5m) for every 45° elbow.

3. In order to use 100-foot (30.5m)

equivalent length of vent pipe with the
model 1670 boiler, consult factory. A
14 inch (356mm) vent pipe may be used.

4. To be used for single boiler installation

only.

5. Note that the Mighty Venter diameters

shown are for both the inlet and the
outlet of the Mighty Venter.

6. The vent pipe reducer kit includes item

D. And one of: Item E, Item G, Item H.
(As shown: varies per model.)

7. Reference Item “L” is used only with the

500 boiler. It is included with the
20069301 Mighty Venter kit.

8. The vent system must be adequately

supported to prevent sagging. But in no
case shall the supports be less than
every three feet (0.9m).

9. The venting system must be sloped

upward not less than ¼ inch per foot
from the furnace to the vent terminal. The
vent system must be installed to prevent
collection of condensate.

10. Side wall vent hood location: Read all

installation/operation information
concerning vent hood location before
installing.

E*

D*

C

A

18" (457mm) minimum
recommended rise
before elbowing to
horizontal run.

K

Equivalent Pipe Length

Calculate as per Notes 2
and 3 below.
Minimum equivalent vent
pipe length is 11' (3.4m)

(Slope: Note 9)

(Supports: Note 8)

Vent pipe is customer supplied

G*

H*

F

J

*

B

Reducer dimensions
For all sizes
(#1, #2, #3, #4)

B*

J

(Note 7)

Clearances to
combustibles:
6" (152mm) sides
8" (203mm) rear

L*

M*

P

N

(Note 10)

Side View

Figure 2. Part identification.

A

NOTE 1

B

C

NOTE 6

D

E

F

G

H

J

K

L, M

N

P

*

*

*

Boiler

Model

Size

Mighty

Venter Kit
Order No.

Power

Venter

Model

Ref.

Boiler

Vent

Outlet

In. (mm)

Vent Pipe

Reducer Kit

Part No.

Reducer Sizes Included In Reducer Kit

Mighty
Venter

Outlet

& Inlet

In. (mm)

Equivalent

Pipe

Length

(Max)
ft. (m)

Vent

Hood

P/N

Vent

Hood

Dia.

in. (mm)

Rough-In

Dimension

In. (mm)

Size

#1

Size

#2

Ref. Vent

Pipe Dia.

In. (mm)

Size

#3

Size

#4

500

20069301

MV-2

10 (254)

20070901

10-8

--

8  (203)

8-6

--

6 (152)

100 (30.5)

D2000401

8.50 (216)

9.0 (229)

600

20069302

MV-3

12 (305)

20070902 12-18

10-8

8  (203)

--

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

715

20069303

MV-3

12 (305)

20070902 12-18

--

10 (254)

10-8

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

850

20069304

MV-4

14 (356)

20070903 14-10

--

10 (254)

10-8

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

1010 20069305

MV4

16 (406)

20070904 15-14

14-12

12 (254)

12-10

10-8

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

1200 20069306

MV-5

16 (406)

20070905 15-14

14-10

10 (254)

--

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)

1430 20069307

MV-5

18 (457)

20070906 18-14

14-10

10 (254)

--

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)

1670 20069308

MV-5

18 (457)

20078907 18-14

14-12

12 (305)

12-10

--

10 (254)

80 (24.4)

D2000403

13.25 (337) 13.75 (349)

1825 20069309

MV-5

18 (457)

20070906 18-14

--

14 (356)

14-10

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)

Содержание MV2

Страница 1: ...nstallation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of...

Страница 2: ...General Information 1a Sizing 3 1b Installer Cautions 3 SECTION 2 Side Wall Vent Hood Location 2a Side Wall Vent Hood Location 4 SECTION 3 Installation 3a Inspection and Unpacking 4 3b Power Venter Mo...

Страница 3: ...1 the National Electric Code NFPA 70 or the Canadian Electrical Code CSA C22 1 and the Occupational Safety and Health Act OSHA 3 Any modifications to the Power Venter motor or wiring may void the warr...

Страница 4: ...peration 17 Ambient temperature surrounding Mighty Venter must not exceed 104 F 40 C 18 To prevent personal injury and equipment damage disconnect power supply to boiler or heater when working on Migh...

Страница 5: ...ludes one Installation Manual specific to the Vent Hood If any items are missing from the package contact Laars Be prepared with your purchase order number and the order number on the shipping documen...

Страница 6: ...nimum equivalent vent pipe length is 11 3 4m Slope Note 9 Supports Note 8 Vent pipe is customer supplied G H F J B Reducer dimensions For all sizes 1 2 3 4 B J Note 7 Clearances to combustibles 6 152m...

Страница 7: ...r 1 4 threaded rod with nuts and washers for mounting see Figure 3 for MV3 see Figure 4 for MV4 and MV5 The Mighty Venter may be mounted in any position as long as the shaft of the motor remains horiz...

Страница 8: ...he electrical box is mounted so that the fan proving switch is in a vertical position 2 Connect the aluminum tubing from the fan proving switch to the Mighty Venter housing using provided fittings 3d...

Страница 9: ...er Junction Box Mighty Venter NOTE The black BK and white W leads from the Mighty Venter to the junction box do not require field wiring on Model MV2 Color Legend BK Black W White R Red Y Yellow BL Bl...

Страница 10: ...LAARS Heating Systems Page 10...

Страница 11: ...Mighty Venter Power Vent Systems Page 11...

Страница 12: ...ville Ontario Canada Return Instructions After faulty component is determined ship inoperative part with proofs of purchase and installation date transportation prepaid directly to one of the addresse...

Отзывы: