Figure 21. Field Connections (TB2)
Figure 22. Field Connections (TB3)
7.D.2 TB2 (for pumps and aux power)
7.D.2.a Boiler Pump
This terminal and the 120V(N) terminal will provide power to the boiler
pump whenever the boiler is running. Use this to power the Low
Loss Header (LLH) pump or a boiler pump in a Primary/Secondary
application. If not using a LLH then this terminal can run power for a
single zone or a zone valve system pump.
7.D.2.b SYS Pump
This terminal and the 120V(N) terminal will provide power to
zone pumps or a zone valve system pump. This terminal cannot
be used if the boiler does not have a dedicated boiler pump that is connected to the boiler pump terminal. When a
system pump and dedicated boiler pump are piped and wired correctly, the control will energize the boiler pump only.
Once the control detects high enough supply water temperature, the system pump will be energized. This feature
helps protect the boiler from condensation due to low inlet water temperature.
7.D.2.c Aux Power
This terminal and the 120V(N) terminal provide
constant high voltage to accessories such as
power vent, combustion air and/or zone relay
systems. Only the field supplied service switches
or the main circuit breaker will interrupt the power
to these terminals.
7.D.3 TB3 (for optional equipment)
DHW Kit - This terminal is only
available if the accessory kit is
purchased. It provides the boiler with
the ability to drive a third pump (the
DHW pump) for ease of installation.
7.D.3.a DHW Pump
These two terminals along with the GND terminal
provide 120V during a DHW call. They are
powered continually as long as DHW Aquastat
terminals are closed.
7.D.3.b DHW Aquastat
These are 24VAC terminals that energize a relay when
they are closed. The relay powers the DHW pump
terminals and communicates with the boiler control to
switch from heating settings to set point targeting.
Pump contacts rated to 5.8 FLA.
DHW Pump contacts rated to 7.5 FLA.
Photo
of DHW
Relay Kit.
CAUTION
Do not exceed 15 Amp circuit. Additional circuits
maybe required for pumps and accessories.