Page 94
149
Flame detected
H or L
Holds if flame detected during Safe Start check up
to Flame Establishing period.
150
Flame not detected
H
Sequence returns to standby and restarts
sequence at the beginning of Purge after the HF
switch opens if flame detected during Safe Start
check up to Flame Establishing period.
154
Purge Fan switch On
H or L
1. Purge fan switch is on when it should be off.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3
and its connections. Make sure the switch
is working correctly and is not jumpered or
welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.
155
Purge fan switch OFF
H or L
156
Combustion pressure and flame ON
H or L
1. Check that flame is not present in the
combustion chamber. Correct any errors.
2. Make sure that the flame detector is wired to
the correct terminal.
3. Make sure the F & G wires are protected from
stray noise pickup.
4. Reset and sequence the module, if code
reappears, replace the flame detector.
5. Reset and sequence the module, if code
reappears, replace the module.
157
Combustion pressure and flame OFF
L
158
Main valve ON
L
1. Check Main Valve terminal wiring and correct
any errors.
2. Reset and sequence the module. If fault
persists, replace the module.
159
Main valve OFF
L
160
Ignition ON
L
1. Check Ignition terminal wiring and correct any
errors.
2. Reset and sequence the module. If fault
persists, replace the module.
161
Ignition OFF
L
164
Block intake ON
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it
is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the
voltage across the switch. Supply voltage
should be present. If not, the Block Intake
Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
165
Block intake OFF
L
172
Main relay feedback incorrect
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
174
Safety relay feedback incorrect
L
175
Safety relay open
L
176
Main relay ON at safe start check
L
178
Safety relay ON at safe start check
L
Содержание MagnaTherm MGH1600
Страница 4: ...LAARS Heating Systems...
Страница 106: ...LAARS Heating Systems Page 102 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 DETAIL Final Assembly...
Страница 121: ...MagnaTherm Boilers and Water Heaters Page 117 Notes...
Страница 122: ...LAARS Heating Systems Page 118 Notes...
Страница 123: ...MagnaTherm Boilers and Water Heaters Page 119 Notes...