LAARS Heating Systems
Page 10
24”
See Table 1 for Suggested Service Top
Clearances
24”
8”
8”
INTAKE / EXHAUST
MAX EQUIVALENT
SIZE DIAMETER
FT.
M
1600
6”
100
30
2000 & 2500 8”
100
30
3000 & 3500 10”
100
30
4000 12”
100
30
Combustion Intake and Vent must be the same size.
Installations in the U.S. require exhaust vent pipe that is CPVC
complying with ANSI/ASTM D1785 F441, polypropylene
complying with ULC S636, or stainless steel complying with
UL1738. Installations in Canada require exhaust vent pipe that
is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with
ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM
D1527, stainless steel, or galvanized material.
To calculate max equivalent length, measure the linear feet of
the pipe, and add 5 feet
(1.5 m)
for each elbow used.
Figure 3. Suggested Service Clearances
SURFACE
INCHES
CM
Front
24
61
Left Side
8
20
Right Side
8
20
Back
24
61
Top, 1600 & 2000
12
30
Top, 2500 & 3000
15
38
Top, 4000
24
61
Table 1. Suggested Service Clearances
Table 2. Required Clearances
SURFACE
INCHES
CM
Front
18
46
Left Side
4
10
Right Side
4
10
Back
11
28
Top
1
2.5
Vent
1
2.5
Table 3. Vent / Air Pipe Sizes
Содержание MagnaTherm MGH1600
Страница 4: ...LAARS Heating Systems...
Страница 106: ...LAARS Heating Systems Page 102 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 DETAIL Final Assembly...
Страница 121: ...MagnaTherm Boilers and Water Heaters Page 117 Notes...
Страница 122: ...LAARS Heating Systems Page 118 Notes...
Страница 123: ...MagnaTherm Boilers and Water Heaters Page 119 Notes...