MagnaTherm Boilers and Water Heaters
Page 9
NOTE :
When located on the same wall, the
combustion air intake terminal must be installed a
minimum of 12” (
30cm)
below the exhaust terminal.
There must also be a minimum horizontal distance
from intake to the exhaust terminal of 84” (
213cm)
See
Figure 7
NOTE :
The unit shall be installed such that the
gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement,
control replacement, etc.).
SECTION 2 Locating the Unit
2.A Locating the unit
This unit may be installed indoors or outdoors. If
installing outdoors in a location that may experience
freezing temperatures, precautions must be taken to
prevent water in the heat exchanger and condensate
inside and outside of the boiler from freezing. Damage
due to freezing water or condensate is not covered by
the warranty.
Choose a location for the unit which allows
clearances on all sides for maintenance and
inspection. See Table 1. Always install the unit on a
firm, level surface. It is recommended that the unit is
installed on a raised 4” pad so that there is elevation for
a condensate neutralizer kit (not included with unit).
The unit should not be located in an area where
leakage of any connections will result in damage to
the area adjacent to the appliance, or to lower floors
of the structure.
When this type of location is not available, install a
suitable drain pan, adequately drained, under the
appliance.
The appliance is design-certified by CSA-
International for installation on combustible flooring;
in basements; in utility rooms or alcoves
. Boilers
must never be installed on carpeting.
The location
for the appliance should be chosen with regard to
the vent pipe lengths and external plumbing.
The unit shall be installed such that the gas ignition
system components are protected from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, control replacement,
etc.).
When vented vertically, the unit must be located as
close as practical to the vertical section of the vent.
If the vent terminal and/or combustion air terminal
terminate through a wall, and there is potential for
snow accumulation in the local area, both terminals
should be installed at an appropriate level above
grade or the maximum expected snow line.
The dimensions and requirements that are shown in
Table 1. should be met when choosing the locations
for the appliance.
2.B Correct Vent Distance from
Outside Wall or Roof Termination
The forced draft combustion air blower in the
appliance has sufficient power to vent properly when
the guidelines in Table 3
are followed.
WARNING
If installing outdoors in a location that may
experience freezing temperatures, provisions
must be made to protect the unit from freeze
damage. Manufacturer does not warranty
damage caused by freezing temperatures.
Содержание MagnaTherm MGH1600
Страница 4: ...LAARS Heating Systems...
Страница 106: ...LAARS Heating Systems Page 102 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 DETAIL Final Assembly...
Страница 121: ...MagnaTherm Boilers and Water Heaters Page 117 Notes...
Страница 122: ...LAARS Heating Systems Page 118 Notes...
Страница 123: ...MagnaTherm Boilers and Water Heaters Page 119 Notes...