LAARS Heating Systems
Page 66
9.H.8
PumpConfiguration
9.H.9
8.5.8
PumpConfiguration
The controller in this unit energizes the appropriate
pump contacts when it receives a call for heat.
Once the call for heat is satisfied, the pumps will
remain on for the defined pump overrun time.
The Boiler, System, and DHW pump terminals are
found on the Main control board TB1-15A through
20A. They are fed 120 Volts internally from the main
power feed. The current rating of the contacts is 7.4
amps, and an appropriately sized contactor must
be supplied and installed by a qualified technician
to ensure proper pump operation. Once the system
has been installed, the “Pump Configuration” menu
will allow the installer to adjust Pump control,
Overrun time and Demand control for the various
pumps in the system.
9.H.10
StatisticsConfiguration
The statistics configuration menu allows the installer
to view Burner Cycles, Burner Run Time, DHW
Pump Cycles, Boiler Pump Cycles, and System
Pump Cycles. This menu is ‘Read-Only’
9.H.11 High Limits
The outlet high limit can be adjusted using the
installer password. After a change is made, the
control will lockout and require a Safety Verification
See Section 9.D for more details on Safety
Verification).
Installers do not have access to change the Outlet
High Limit Response. That is only accessible to the
factory.
9.H.12 Stack Limits
Stack limit delay, response and setpoint can be
changed ONLY BY THE FACTORY.
Содержание MagnaTherm MGH1600
Страница 4: ...LAARS Heating Systems...
Страница 106: ...LAARS Heating Systems Page 102 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 DETAIL Final Assembly...
Страница 121: ...MagnaTherm Boilers and Water Heaters Page 117 Notes...
Страница 122: ...LAARS Heating Systems Page 118 Notes...
Страница 123: ...MagnaTherm Boilers and Water Heaters Page 119 Notes...