background image

 

Outdoor temperature 
alarm 

32ºF (low) 

104ºF (high) 

Indoor humidity alarm 

35%RH (low) 

65%RH (high) 

Outdoor humidity alarm 

45%RH (low) 

70%RH (high) 

Wind chill alarm 

50ºF (low) 

86ºF (high) 

Dew point alarm 

32ºF (low) 

68ºC (high) 

Rainfall 24h alarm 

1.96 inches 

Rainfall 1h alarm 

0.03 inches 

Wind Speed 

1.0 mph (low) 

62 mph (high) 

Wind direction alarm 

None set 

 
 
Time & Date (LCD Section 1) 

If the WWVB icon (icon 2) is ON and not flashing, it means that the 
WWVB radio-controlled time and date are has been received. Press 
the PLUS (+) key to change the format of date display between 
date/month/year, weekday/date/month, seconds, alarm set time and 
time zone. 
 
 

 

 

Note: 

 

All alarm default values are deactivated at the start up and any alarm 
must be activated by the user otherwise it will not sound.  

 
 

 

Weather forecasting (LCD Section 1) 

11. 

Function Description of the Weather Station 

The three weather icons Sunny, Cloudy and Rainy represent the 
weather forecasting. There are also two weather tendency indicators 
to show the air pressure tendency either side of the weather icons.  

 
After setting up, the following data will be displayed in different 
sections on the LCD. If this is not the case please observe the notes 
on “

Interferences

” below.

 

 
 

 

 

 

 

 

 

Sunny

Rainy 

Cloudy

 

 

 

Notes to hPa sensitivity setting for weather forecasting: 

 

The hPa (Hekto-Pascal) pressure sensitivity can be set to suit the 
user’s requirement for weather forecasting from 6 inHg, 9 inHg to 12 
inHg (see 

Basic Programming

 below).  For areas that experience 

frequent changes in air pressure (which does not necessarily reflect a 
change in the weather) requires a higher inHg setting compared to an 
area where the air pressure is stagnant. For example if 6 inHg is 
selected, then there must be a fall or rise in air pressure of at least 6 
inHg before the weather station will register this as a change in 
weather. 

 
 
 
 
 
 
 
 
 

 

 

Air Pressure (LCD Section 1) 

 

The air pressure reading is displayed here. Press the PRESSURE 
key to toggle between relative and absolute air pressure displays. 

 
 

 

 

Notes to Absolute and Relative Air Pressure: 

 

LCD Section 3: 

Wind direction, wind speed, and 
respective alarms sections

 

LCD Section 2

Indoor and outdoor temperature and 
relative humidity, wind chill, dew 
point, rainfall, and respective alarms 
sections

LCD Section 1: 

Time, date, seconds, time zone, 
weather forecasting icons with 
tendency arrows, air pressure, 
and respective alarms sections

 

Содержание WS-2310

Страница 1: ...10 Resetting factory settings 11 Function description 12 Operation keys 13 Basic programming modes 14 MIN MAX programming modes 15 Alarm programming modes 16 Auto memory for stored values 17 Accessor...

Страница 2: ...wind and rain sensors are connected to the thermo hygro sensor for operating power and rely on it to communicate to the base station Weather data sent from the thermo hygro sensor can be done by wire...

Страница 3: ...the data to the base station Operating power is taken from the thermo hygro sensor using a 32ft cable connection Features of Rain sensor The rain sensor measures the rainfall and sends the data to the...

Страница 4: ...hree sockets for the wind sensor rain sensor and the base station 2 Connect the attached cables of wind and rain sensors to the corresponding sockets of the thermo hygro sensor by clicking them into p...

Страница 5: ...ection for power back up in case of AC power failure A loss of power would desynchronize the base station and the sensor and no weather data will be received To Synchronize the units so that the weath...

Страница 6: ...time intervals for the wind readings However the current wind speed or direction will be displayed once the time reading interval is reached For rainfall the interval readings may take up to 2 minute...

Страница 7: ...ignals are received the system can be affixed Also if you have selected to use cable connection ensure that distances can reach all desired locations before affixing any unit permanently Once the wind...

Страница 8: ...gro Sensor However if you wish to make a full reset of the base station and return to the original factory settings simultaneously press and hold the PRESSURE and WIND keys for about 5 seconds The bas...

Страница 9: ...e displayed in different sections on the LCD If this is not the case please observe the notes on Interferences below Sunny Rainy Cloudy Notes to hPa sensitivity setting for weather forecasting The hPa...

Страница 10: ...chill Outdoor dew point Rainfall 24h Rainfall 1h Rainfall total Notes to Dewpoint and Windchill Air can at a certain temperature only carry a certain amount of water water vapor which also increases a...

Страница 11: ...current maximum minimum display modes Indoor temperature and humidity Outdoor temperature and humidity Outdoor wind chill Outdoor dew point Rainfall 24h 1h total WIND key To toggle between the followi...

Страница 12: ...the manually set time and date and no further reception is attempted until the following day The manual setting takes the user through the following modes 1 8 level LCD contrast setting default level...

Страница 13: ...Setting Alarms For alarm setting press the ALARM key once while in normal operation mode to enter the normal alarm time and by further pressing the ALARM key will toggle through each of the alarm mode...

Страница 14: ...reach the indoor humidity high alarm set mode 3 Press and hold the SET key to enter the indoor humidity high setting values digits will start flashing and set the desired indoor humidity high by usin...

Страница 15: ...time alarm 2 Continue to press the ALARM key until you reach the rain 1 hour alarm set mode 3 Press and hold the SET key to enter the rain setting values digits will start flashing and set the desire...

Страница 16: ...Alarm BUZZER OFF The time and all the weather alarms may have buzzer sound set to OFF by holding the MINUS key down for about 3 seconds in normal display mode and the BUZZER OFF icon appears on the b...

Страница 17: ...75 2 F with a pre set hysteresis of 1 8 F so that the alarm can be produced again Hysteresis values for the various weather data types are given in the following table For your convenience additional...

Страница 18: ...the low battery indicator will light up on the LCD Please participate in the preservation of the environment by properly disposing of all used up batteries and accumulators at designated disposal poi...

Страница 19: ...n the housing and screen of the base station only with a soft damp cloth Do not use abrasives or solvents Ensure that the rain sensor does not collect leaves or other dirt by checking the funnel for b...

Страница 20: ...of 30 000 ft is around 8 85 inHg Resolution 0 01 inHg Relative humidity checking interval every 30 seconds Alarm duration 2 minutes approx Power consumption Base Station Batteries 3 x AA IEC LR6 1 5V...

Отзывы: