6.4.3. Limiting through currents
Inside
E20-10
circuits AGND, GND, GND*, presenting on module connectors are
. This places certain restrictions on maximum permissible through currents
through circuits AGND-GND-GND*.
Attention!
Maximum permissible through currents exceeding can cause
E20-10
failure
.
Table6-5. Maximum permissible through currents
Circuit
Maximum allowable output current
AGND-GND
0.1 А
AGND-GND*
0.1 А
GND-GND*
0.7 А
6.4.4. External power supply input characteristic
When
E20-10
is energized not from AD adapter including in delivery package (p.
) and
from external direct current source the following parameters shall be taken into account:
Table 6-6. External power supply input characteristics
Parameter
Value
Rev. “А”, “В”
Rev. В.01
Operating voltage range
+9.0…+27 V
(engagement threshold
+9,5 V)
+8.0…+40 V
Maximum permissible voltage
−30…+30 V
−45…+45 V
Power input under operating mode with off-
load output circuits
E20-10
.
max. 5 W (rev. А)
min 4.5 W (rev. В)
max. 4.5 W