4.4 Connection to the measured object
KEW 2062/2062BT
- 15 -
KEW 2062/2062BT
DANGER
●
Care should be taken so as not to short-circuit the power line with the metal ends of the
test lead at connection. In addition, do not touch the metal tips.
●
The tips of the current sensor jaws are designed so as not to short-circuit the power line of
the object to be tested but be careful when measuring an un-insulated conductor.
●
Keep your fingers behind the barrier during a measurement.
Barrier: provides protection against electrical shock and ensuring the minimum required
clearance and creepage distances.
For accurate measurement:
●
The declared measurement accuracy is guaranteed where the conductor to be measured
is placed at the center of the current clamp sensor.
●
Care should be taken so as not to pinch the conductors with the tips of the jaws.
●
Confirm and harmonize the wiring configuration of the measurement line and KEW
2062 / KEW2062BT.
● When clamping onto
a conductor, make the arrow mark point towards the load side;
otherwise, polarity of active power (P) will be reversed and displayed.
Arrow mark
● Never clamp two or more conductors.
KEW 2062/2062BT
Chapter 5 Settings
KEW 2062/2062BT
- 16 -
Chapter 5 Settings
Before starting a measurement, adjust the following settings.
* Wiring configuration, frequency of the voltage to be measured,
and VT/ CT ratio, if necessary.
Set the functin switch to “
” to adjust settings.
Note
● Turning the function switch before confirming the altered settings clears all the changes
you made. Confirm the altered settings, and then turn the function switch.
Item selection (Switch the displayed items)
Press the item switching button
[◄►] to toggle the displayed
items and confirm the desired item with the mode button.
Alter the values of each item with the item switching button
[◄►], and
then press the mode button again to confirm the
change. The display returns to the selection screen.
The followings are the default settings. System reset restores the altered changes to the default.
Wiring configuration
VT ratio
CT ratio
Frequency of nominal voltage Backlight
[◄►]
[◄►]
[◄►]
[◄►]
[◄►]
[◄►]
[◄►]
Item switching button
[◄►]
: toggles setting items
Mode button : confirms selection and change.
System reset
Buzzer
www.
.com