ADVR-16-400HZ

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SECTION 3 : CONNECTION TERMINAL 

3.1 

P1,  P2

Power  Input  Terminals  from  60  to  300 

Vac 400 Hz -16A rated. 

 

3.2 

F+, F-

Maximum Output current 16A. 

 

3.3 

VS1, VS2

Voltage sensing input terminals, Volts 

selected using DIP SW1 for 220V or 440V. 

 

3.4 

K,  L

Load  Current  Compensation  (Droop),  CT 

secondary  current  input  selected  by  using  DIP 
SW  1A  or  5A  (If  droop  not  used  leave  terminals 
open). 

 

3.5 

VR1, VR2

External Voltage trim use, 2K ohms 1 

watt trimmer for +/- 5% voltage adjustment. Keep 
terminals shorted when not in use. 

 

3.6 

A1,  A2

Analogue  Voltage  Input  terminals  used 

for Power Factor correction from a external PLC- 
The PLC controls provides a DC voltage signal to 
adjust  the  generator  voltage.  Max.  Adjustment 
range is +/- 5 Vdc. Keep terminals open when not 
used. 

 
3.7 

DIP Switch 

 

SW1

OFF 220 Vac (170 to 260 Vac) 

 

ON 440 Vac (340 to 510 Vac) 

 

SW2

OFF CT Secondary Input 1A 

 

ON CT Secondary Input 5A 

 

SW3

No use. 

 

SW4

OFF Over excitation protection enabled 

 

ON Over excitation protection disabled 

 
3.8 

LED Indicator 

 

U/F

Under Frequency Indicator 

 

O/E

Over Excitation Indicator 

 

SECTION 4 : ADJUSTMENT AND SETTING 

4.1 

TRIM works together with a bias voltage applied 
to terminals A1 and A2. This signal is supplies by 
an  external  Power  Factor  Paralleling  PLC.  Use 
the TRIM potentiometer to adjust the DC voltage 
input  that  controls  the  level  of  the  generator

’s 

output  voltage.  When  set  counter-clockwise  the 
control  level  is  zero, and if moved clockwise  the 
maximum  control  range  is  10%.  The  signal 
connected to A1 and A2 can be unipolar (0,+) or 
bipolar (+,

). Check  with the manufacture of the 

Paralleling control PLC. 

 
4.2 

DROOP

Select  switch  K  or  L  pending  on  the 

secondary  current  of  the  CT  that  you  are  using. 
Voltage  droop  works  when  the  CT  and  the  AVR 
senses  that  the  output  of  the  generator  voltage 
and current waveforms are out of synch and the 
AVR  droops  the  output  voltage  of  the  generator 
to correct it. 

 
4.3 

STAB

If  the  generator  output  voltage  oscillate, 

adjusting  the  STAB  potentiometer  will  stabilize 
the  output  voltage,  over  adjustment  will  result  in 
high  voltage variation  when load is applied.  Use 
an  analog  type  multimeter  when  making  this 
adjustment.  Connect  the  meter  to  terminals  F+ 
and F-  and slowly  adjust  STAB potentiometer to 
the point when the pointer stops moving. 

 
4.4 

VOLT

Move to set the generator output voltage. 

Set DIP Switch 1 to the generator working voltage. 

 
 

Set SW1 to OFF (220V) for use from 170 to 260 Vac 

 

Set SW1 to ON (440V) for use from 340 to 510 Vac 

 

When using and external VR set it to the central 
position and adjust the AVR VOLT trim to the 
rated voltage.

88.0

112.0

138.0

162.0

18.3

43.0

   5.2

ADVR

-16

Unit : mm

 

Figure 1

 

Outline Drawing 

ATTENTION 

1.  AVR  can  be  mounted  directly  on  the  engine,  genset, 

switchgear,  control  panel,  or  any  position  that  will  not 
affect  operation.  For  dimension  reference,  please  see 
Figure 1. 

2.  All  voltage  readings  are  to  be  taken  with  an 

average-reading  voltmeter  Meggers  and  high-potential 
test  equipment  must  not  be  used.  Use  of  such 
equipment could damage the AVR. 

3.  Secure  all  wiring  connection.  Do  not  install  AVR  at  a 

place with high vibrations to prevent loose connections. 
For safety do not touch the heat sink while in operation. 

4.  Terminal

“Fast-On” terminals 6.35mm (1/4 inch) & With 

4mm crimping terminal. 

5.  Improper  setting  of  under-frequency  protection  could 

cause the output voltage of the unit to drop or become 
unstable under with changes in load. Avoid making any 
changes to the U/F setting unless necessary. 

6. Turn off O/E in AVR when paralleling. 

Содержание ADVR-16-400HZ

Страница 1: ...ters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 16 400HZ Universal Hybrid Analog Digital Voltage Regulator Operation Manual Universal 400Hz Intermediate Frequency 16 Amp Half Wave Self Excited Generator Automatic Voltage Regulator For Aviation and Military Spec 400Hz Generators ...

Страница 2: ... Input Voltage 170 510 Vac 1 phase 2 wire CT 1A or 5A greater than 5VA DIP switch setting Frequency 50 60 Hz DIP switch setting Sensitivity 7 PF 0 5 Power Input Analogue Voltage Input Voltage 60 300 Vac 1 phase 2 wires Max 5 Vdc 10 3 Vdc Excitation Output Under Frequency Protection Factory Presets 240V 1 phase Continuous 63 Vdc 16A 50 60 Hz DIP switch setting Max 90 Vdc 20A for 10 secs Resistance ...

Страница 3: ...ect switch K or L pending on the secondary current of the CT that you are using Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it 4 3 STAB If the generator output voltage oscillate adjusting the STAB potentiometer will stabilize the output voltage ov...

Страница 4: ...n is not required the user can disable this function by switching DIP switch SW4 to ON position vice versa SECTION 5 NOTICE OF USE 5 1 Installation Notice Refer to Figure 2 and 4 5 1 1 Only a trained professional can Installation calibrate and inspections this AVR 5 1 2 Install this AVR inside the generator enclosure away from moisture corrosion and from any easy to reach area 5 2 Generator Operat...

Страница 5: ... EA16A EXT VR K A1 VR1 VR2 Field P2 P1 VS1 F VS2 F A2 L GEN T R S N Figure 4 220V Connection GEN EXT VR K VR1 VR2 A1 F P2 P1 VS1 F VS2 A2 L T N R S EA16A Field Figure 3 Paralleling Connection Figure 5 380 480V Connection Field EXT VR EA16 VR2 VR1 A2 A1 F VS1 P1 P2 F L VS2 K GEN T N S R Aux Winding 60 300v Figure 6 Auxiliary Winding ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 400HZ ADVR 16 400H...

Страница 6: ...r adjustment is made Read start procedure carefully and adjust again U F protection activated Increase generator speed U F activated Incorrect voltage selection Read user s manual to select correct voltage Over output voltage Poor adjustment is made Read start procedure carefully and adjust again Incorrect voltage selection Read user s manual to select correct voltage Output voltage unstable Hunti...