SECTION 7 : TROUBLE SHOOTING 

SYMPTOM 

POSSIBLE CAUSES 

SOLUTIONS 

Voltage does not 

build up 

Residual voltage below 5 Vac 

Reference from section 6. Field Flashing 

F+, F- polarity reversed 

F+ and F- reverse the connection 

F+, F-, P1, P2, VS1, VS2 not connected  Reference from Figure 4 and 5 connection 

Burnt fuse 

Change fuse 16A 500V 

Ext. Switch (Breaker) not turned on 

Switch on (ON) 

Engine RPM under speed 

Increase engine speed / frequency above 25 Hz 

Low output voltage 

Poor adjustment is made 

Read start procedure carefully and adjust again 

U/F protection activated 

Increase generator speed 

U/F activated / Incorrect voltage selection 

Read user’s manual to select correct voltage 

Over output voltage 

Poor adjustment is made 

Read start procedure carefully and adjust again 

Incorrect voltage selection 

Read user’s manual to select correct voltage 

Output voltage 

unstable (Hunting) 

Poor adjustment is made 

Read start procedure carefully and adjust again 

Field  voltage  requirement  lower  the 
rang of regulator 

Connect  appropriate  resistors  in  series  to 
increase total impedance 

  Use only the replacement fuses specified in this user manual. 

  Appearance and specifications of products are subject to change for improvement without prior notice. 

Содержание ADVR-16-400HZ

Страница 1: ...ters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 16 400HZ Universal Hybrid Analog Digital Voltage Regulator Operation Manual Universal 400Hz Intermediate Frequency 16 Amp Half Wave Self Excited Generator Automatic Voltage Regulator For Aviation and Military Spec 400Hz Generators ...

Страница 2: ... Input Voltage 170 510 Vac 1 phase 2 wire CT 1A or 5A greater than 5VA DIP switch setting Frequency 50 60 Hz DIP switch setting Sensitivity 7 PF 0 5 Power Input Analogue Voltage Input Voltage 60 300 Vac 1 phase 2 wires Max 5 Vdc 10 3 Vdc Excitation Output Under Frequency Protection Factory Presets 240V 1 phase Continuous 63 Vdc 16A 50 60 Hz DIP switch setting Max 90 Vdc 20A for 10 secs Resistance ...

Страница 3: ...ect switch K or L pending on the secondary current of the CT that you are using Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it 4 3 STAB If the generator output voltage oscillate adjusting the STAB potentiometer will stabilize the output voltage ov...

Страница 4: ...n is not required the user can disable this function by switching DIP switch SW4 to ON position vice versa SECTION 5 NOTICE OF USE 5 1 Installation Notice Refer to Figure 2 and 4 5 1 1 Only a trained professional can Installation calibrate and inspections this AVR 5 1 2 Install this AVR inside the generator enclosure away from moisture corrosion and from any easy to reach area 5 2 Generator Operat...

Страница 5: ... EA16A EXT VR K A1 VR1 VR2 Field P2 P1 VS1 F VS2 F A2 L GEN T R S N Figure 4 220V Connection GEN EXT VR K VR1 VR2 A1 F P2 P1 VS1 F VS2 A2 L T N R S EA16A Field Figure 3 Paralleling Connection Figure 5 380 480V Connection Field EXT VR EA16 VR2 VR1 A2 A1 F VS1 P1 P2 F L VS2 K GEN T N S R Aux Winding 60 300v Figure 6 Auxiliary Winding ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 400HZ ADVR 16 400H...

Страница 6: ...r adjustment is made Read start procedure carefully and adjust again U F protection activated Increase generator speed U F activated Incorrect voltage selection Read user s manual to select correct voltage Over output voltage Poor adjustment is made Read start procedure carefully and adjust again Incorrect voltage selection Read user s manual to select correct voltage Output voltage unstable Hunti...

Отзывы: