background image

 

___________________________________________________________________________________________ 

4

 

ADVR-16-400HZ

 

Figure 2

 

Manual Field Flash 

 

NOTE 

If the external VR is not used, short terminal VR1 
and VR2. 

 
4.5 

U/F

Under Frequency protection setting. 

 

At 400 Hz U/F factory set at 360Hz 

 
 

To  adjust  the  U/F  setting,  select  the  correct 
system frequency, start engine and adjust engine 
speed to the required U/F frequency (for example 
360  Hz),  slow  adjust  U/F  potentiometer  until  the 
U/F red LED turn ON, returning the engine speed 
to normal turn the LED off. Adjustment range for 
400Hz system is 420 to 320 Hz 

 

Function of the Under Frequency trim pot

 

4.5.1  During  start  up  or  shutdown,  the  engine  speed 

changes going over or under its rated RPM (Hz). 
This  AVR  has  an  Under  Frequency  circuit  to 
protect  the  AVR  and  exciter;  you  do  not  need  to 
disconnect the AVR when idling the engine. 

 
4.5.2  If load is hi

gher than the generator’s capacity, the 

Under 

Frequency 

activates, 

reducing 

the 

generator’s voltage preventing generator overload. 

 

4.6 

Over Excitation Protection

 

4.6.1  This  AVR  has  over  Excitation  Protection 

preventing  the  generator  from  working  under 
unusually  high  excitation.  Excitation  Protection 
includes generator overload, accident removal of 
sensing  wires,  and  incorrect  voltage  setting. 
When problems occur, O/E protection will activate 
and shutdown AVR’s excitation output (Delay up 
to  5  seconds)  which  makes  the  generator 
gradually  drop  to  its  minimum  voltage  (residual 
voltage).  Meanwhile  the  O/E  LED  stays  ON  and 
keeps  functioning,  you’ll  need  to  stop  the 
generator  for  about  10  seconds  and  restart  the 
AVR  to  be  able  to  work  properly.  When  working 
the  generator  in  parallel  this  protection  is  not 
required,  the  user  can  disable  this  function  by 
switching  DIP  switch  SW4  to  ON  position,  vice 
versa. 

 
 

SECTION 5 : NOTICE OF USE 

5.1 

Installation Notice

(Refer to Figure 2 and 4). 

5.1.1  Only,  a  trained  professional  can  Installation, 

calibrate and inspections this AVR. 

5.1.2  Install  this  AVR  inside  the  generator  enclosure 

away from moisture, corrosion and from any easy 
to reach area. 

 

5.2 

Generator Operation Notice

 

5.2.1  During operation, the temperature on the surface 

of the AVR can reach higher the 60 

˚C / 140 ˚F. 

5.2.2 

“DANGER” When the AVR is working never touch 
or  ground  the  heat  sink  on  the  AVR.  The  AVR 
heat sink is an electrically live terminal. 

 
 

A  warning  sticker  is  in  place  on  top  of  the  heat 
sink. 

 

 

 

SECTION 6 : FIELD FLASHING 

When  the  regulator  is  installed  correctly  but  the 
generator  is  failed  to  generate  power.  Besides  carbon 
brushes  were  worn  out,  here  are  two  possible  causes 
below. 
 

6.1 

The polarity of field is reversed 

 

Solution

Exchange the connection of F+ and F-. 

 

6.2 

The  residual  voltage  is  less  than  5  Vac, 

Solution 1

 

 

6.2.1  Shut  down  generator,  disconnect  the  wiring 

between  AVR  and  generator  then  flash  the  field. 
Flashing  duration  =  3  seconds.  (See  wiring  in 
Figure 2) 

 

Resistor 3 

– 5 ohms for full wave AVR 

 

Resistor 5 

– 10 ohms for half wave AVR 

 

 

Warning

!!

    Over  field  flashing  may  damage 

the field winding of generator. 

 

6.2.2  Restart  generator  and  measure  the  residual 

voltage by AC Voltmeter, if it is still less than 5 Vac, 
repeat  the  previous  process,  after  several  times, 
the  residual  voltage  still  cannot  be  built,  Kutai 
EB500 is strongly recommended, see Figure 2. 

 

Field

SW

R

-

+

V

F+

F-

BATT.

~

G

~

T

S

R

 

 

WARNING 

Overly  field  flashing  may  damage  the  AVR  or 
generator excitation winding. 

Please make sure you have read and understand 
the  contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product  and 
other equipments. 

Содержание ADVR-16-400HZ

Страница 1: ...ters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 16 400HZ Universal Hybrid Analog Digital Voltage Regulator Operation Manual Universal 400Hz Intermediate Frequency 16 Amp Half Wave Self Excited Generator Automatic Voltage Regulator For Aviation and Military Spec 400Hz Generators ...

Страница 2: ... Input Voltage 170 510 Vac 1 phase 2 wire CT 1A or 5A greater than 5VA DIP switch setting Frequency 50 60 Hz DIP switch setting Sensitivity 7 PF 0 5 Power Input Analogue Voltage Input Voltage 60 300 Vac 1 phase 2 wires Max 5 Vdc 10 3 Vdc Excitation Output Under Frequency Protection Factory Presets 240V 1 phase Continuous 63 Vdc 16A 50 60 Hz DIP switch setting Max 90 Vdc 20A for 10 secs Resistance ...

Страница 3: ...ect switch K or L pending on the secondary current of the CT that you are using Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it 4 3 STAB If the generator output voltage oscillate adjusting the STAB potentiometer will stabilize the output voltage ov...

Страница 4: ...n is not required the user can disable this function by switching DIP switch SW4 to ON position vice versa SECTION 5 NOTICE OF USE 5 1 Installation Notice Refer to Figure 2 and 4 5 1 1 Only a trained professional can Installation calibrate and inspections this AVR 5 1 2 Install this AVR inside the generator enclosure away from moisture corrosion and from any easy to reach area 5 2 Generator Operat...

Страница 5: ... EA16A EXT VR K A1 VR1 VR2 Field P2 P1 VS1 F VS2 F A2 L GEN T R S N Figure 4 220V Connection GEN EXT VR K VR1 VR2 A1 F P2 P1 VS1 F VS2 A2 L T N R S EA16A Field Figure 3 Paralleling Connection Figure 5 380 480V Connection Field EXT VR EA16 VR2 VR1 A2 A1 F VS1 P1 P2 F L VS2 K GEN T N S R Aux Winding 60 300v Figure 6 Auxiliary Winding ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 ADVR 16 400HZ ADVR 16 400H...

Страница 6: ...r adjustment is made Read start procedure carefully and adjust again U F protection activated Increase generator speed U F activated Incorrect voltage selection Read user s manual to select correct voltage Over output voltage Poor adjustment is made Read start procedure carefully and adjust again Incorrect voltage selection Read user s manual to select correct voltage Output voltage unstable Hunti...

Отзывы: