0x0034 Script Status Register
In this register you will find information about the current status of the
scripts.
Modbus Register
0x0034
Value Range
0x00-0xff
Default Value
0x00
Number of bytes available
1
Permanently stored
No
Access
Read Only
Meaning
0
The running script is in the initialisation
phase
1
The script is running cyclically
2
The running script is waiting for data input
or for a waiting period to elapse
3
The script was stopped or no script for run-
ning is loaded or running script is deactiv-
ated
4
Script cannot run due to a serious error
0x0035 Script Loop Register
In this register you have the option to monitor whether your script is
running. During each run of the script, the value in the register is
incremented.
Modbus Register
0x0035
Value Range
0x0000- 0xffff
Initial value
0
Number of bytes available
2
Permanently stored
No
Access
Read Only
Memory Register