Kübler Group
4 Installation
English
Operation Manual R60071.0009 - 04
EN | 23
4.2.4 Terminal Assignment
IMG-ID: 9007199428518923
IMG-ID: 9007199428525835
IMG-ID: 9007199428522379
+V:
Encoder supply vV DC
0 V:
Encoder ground GND (0V)
D+, D-:
Data signal
C+, C-:
Clock signal
A, A\:
Incremental output Channel A (Cosine)
B, B\:
Incremental output Channel B (Sine)
RS485 specifies a standard voltage range for the slave sup-
ply of 7 ... 12 V DC (including the tolerances). The supply
voltage is measured on the slave; the maximum voltage drop
over the cable length must be considered accordingly when
dimensioning the master supply.
RS485 specifies a maximum current consumption by the
slave of 250 mA at 7 V DC.
4.2.5 Connecting the Connecting Wires
ATTENTION
Destruction of the electronics
When confectioning the sensor cable, always take care to en-
sure sufficient ESD protection.
• Before connecting the connecting wires, check the assign-
ment of the single wires.
• After connecting, check the proper presence of the supply
voltage and the proper functioning.