Manual
Limes LA10 / BA1
Absolute Magnetic Length Measurement System
7.5 Termination independence
With the CANopen interface variant, depending on the order code, a 120 Ω terminating
resistor is integrated in the interface input. The SSI interface always integrates a terminating
resistor.
Example „emulation switching“
Parameter
Description
min.
typ.
max.
Unit
Medium voltage
Um (sin)
Um (cos)
2.4
2.5
2.6
V
Amplitude
sin – sin
cos – cos
400
500
600
mV
Relationship
(sin – sin)/
(cos – cos)
0.9
1.0
1.1
–
Difference of Phase
85
90
+/- 10%
95
°degree
Distortion factor
K
–
–
3
%
7.6 Offset
After the installation of the magnetic tape and the measuring system (sensor head), a value is
transmit by the interface. Because this value does not conform to the machine zero point, an
offset should to be deposited at the controller side.
NOTICE!
An offset is necessary in each case of a replacement of the EMAX encoder
(sensor head) or magnetic tape.