Absolute Magnetic Length Measurement System
The following baud rates are standardised by CiA:
Baudrate table 0x00
Baudrate:
1000 kBit/s
800 kBit/s
500 kBit/s
250 kBit/s (default value)
125 kBit/s
100 kBit/s
50 kBit/s
Again, the device answers with an error code:
0x13
Error code
Error extension
reserved
Error code 0 means that the command has been accepted - Error code 1 indicates an invalid
Node ID.
The remaining error codes are reserved. The error extension includes manufacturer-specific
information can only be used in case of error code 0xFF.
Both network-specific parameters have now been modified, and the new
parameters must be saved using „Store Configuration“:
0x17
reserved
Again, the device answers with an error code:
0x17
Error code
Error extension
reserved
Error code 0 means that the command has been accepted - Error code 1 indicates an invalid
Node ID.
The remaining error codes are reserved. The error extension includes manufacturer-specific
information can only be used in case of error code 0xFF.
To complete the LSS service, the device is switched back from the LSS configuration mode to
the Preoperational mode with the command „Switch Mode Global“:
0x04
0x00
reserved