Backup time
Long run unit depends on the capacity of external batteries
Typical recharge
time(standard modle)
4 hours recover to 90% capacity (Typical)
Charging voltage
27.4
VDC
±1%
41.0
VDC
±1%
27.4
VDC
±1%
41.0
VDC
±1%
54.7
VDC
±1%
82.1
VDC
±1%
54.7
VDC
±1%
82.1
VDC
±1%
82.1
VDC
±1%
109.4
VDC
±1%
82.1
VDC
±1%
109.
4
VDC
±1%
Charge current
1A
12A max,
can
be setting by
LCD
1A
12A max,
can be
setting by
LCD
1A
12A max,
can be
setting by
LCD
SYSTEM FEATURES
Overload
@35
℃
Line
Mode
Battery
Mode
Ambient Temp.<35
℃
105%~110%: UPS transfer to bypass after 10minuteswhen the utility is normal
110%~130%: UPS transfer to bypass after 1minute when the utility is normal
130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
>150%: UPS transfer to bypass immediately when the utility is normal
35
℃
<Ambient Temp.<40
℃
105%~110%: UPS transfer to bypass after 1minute when the utility is normal
110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal
>130%: UPS transfer to bypass immediately when the utility is normal
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
EPO (optional)
Shut down UPS immediately
Audible & Visual alarms
Line Failure, Battery Low, Overload, System Fault
Comunication interface
USB(or RS232), SNMPcard(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature
0
℃~
40
℃
Storage temperature
-25
℃~
55
℃
Humidity range
20-90 % RH @ 0- 40°C (non-condensing)
Altitude <
1500m
Noise level
Less than 50dBA at 1 Meter
PHYSICAL
Dimension W×H×D
(mm)
144*
209*
293
144*
209*
399
144*
209*
293
144*
209*
293
144*
209*
399
191*
337*
460
144*
209*
399
144*
209*
399
191*
337*
460
191*
337*
460
144*
209*
399
144*
209*
399
Net Weight (kg)
9.8 14.4 4 4.1
17 27.1 6.7 6.8 27.6 32.8
7.3 7.4
STANDARDS
Safety
IEC/EN62040-1,IEC/EN60950-1
EMC
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
* Derate to 80% of capacity when the output voltage is adjusted to 200/208VAC
** Product specifications are subject to change without further notice.