12
04
Battery capacity setting
Press Func button to change the
setting (Battery capacity range is
1-200Ah).
Press UP button
▲
to select the
previous setting.
Press DOWN
▼
button to select the
next setting.
05
EOD voltage setting
Press Func button to change the
setting(160/167/175/180.)
default setting
:
175(1.75V /cell)
Press UP button
▲
to select the
previous setting.
Press DOWN
▼
button to select the
next setting.
06
Bypass voltage upper limit
setting
Press Func button to change the
setting(The bypass voltage upper limit
range is 230-264Vac ).
Press UP button
▲
to select the
previous setting.
Press DOWN
▼
button to select the
next setting.
07
Bypass voltage lower limit
setting
Press Func button to change the
setting(The bypass voltage lower limit
range is 170-220Vac).
Press UP button
▲
to select the
previous setting.
Press DOWN
▼
button to select the
next setting.