7. Specification 

MODEL 

1KVA(S) 

1KVA(H) 

2KVA(S) 

2KVA(H) 

3KVA(S) 

3KVA(H) 

PHASE 

Single phase with ground 

Capacity (VA/Watts) 

1000VA / 900W 

2000VA / 1800W 

3000VA / 2700W 

INPUT  

Nominal voltage 

200/208/220/230/240VAC 

Operating  
voltage 
range 

Low line 
transfer 

160Vac±5% @100%-80% load; 

140Vac±5% @80%-70% load; 
120Vac±5% @70%-60% load; 

110Vac±5% @60%-0% load; 

(Ambient Temp. <35

Low line 
comeback 

175Vac±5% @100%-80% load; 

155Vac±5% @80%-70% load; 
135Vac±5% @70%-60% load; 

125Vac±5% @60%-0% load; 

(Ambient Temp. <35

High line 
transfer 

300Vac ±5% 

High line 
comeback 

290Vac ±5% 

Operating frequency 
range 

40-70Hz 

Power factor 

0.99@100% load(Nominal Input Voltage) 

Bypass voltage range 

Bypass high voltage point

 

230-264

: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac) 

Bypass low voltage point

 

170-220

: setting the low voltage point in LCD from 170Vac to 220Vac. (Default: 170Vac) 

Generator input 

Support 

OUTPUT 

Output voltage 

200/208/220/230/240Vac 

Power factor 

0.9 

Voltage regulation 

±1% 

Frequency 

Line Mode 
(synchroni

zed range) 

47-53Hz or 57-63Hz 

Bat. Mode 

(50/60±0.1)Hz 

Crest factor 

3:1 

Harmonic distortion 
(THDv) 

3% THDwith linear load   

6% THD with non linear load 

Waveform  

Pure Sinewave 

Transfer 
time 

AC mode 
<->Batt. 
mode 

Zero 

Inverter 
<-> 
bypass 

4ms(Typical) 

Efficiency 

Line mode 

88% 92%  92% 

Batt mode 

85%

86% 85% 86% 

87% 88%  87% 88%  89% 90%  89%

90%

BATTERY 

Battery Type 

12V9AH 

depends on 

the capacity 

of external 

batteries

 

12V9AH

 

depends on 

the 

capacity of 

external 

batteries

 

12V9AH

 

depends on 

the capacity 

of external 

batteries

 

Содержание UDC9101RTH

Страница 1: ...Uninterruptible Power Systems 1 2 3KVA Operation Manual 4256 1749 E...

Страница 2: ...ut high frequency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect intelligent monitoring and network functions smart...

Страница 3: ...uide 3 2 Installation and setup 4 2 1 Unpack checking 4 2 2 Real panel view 4 2 3 LCD control panel 6 2 4 Setup the UPS 6 3 Operations 7 3 1 Button operation 7 3 2 LCD display 8 3 3 UPS setting 11 3 4...

Страница 4: ...nt The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist env...

Страница 5: ...voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batter...

Страница 6: ...use 2 1Unpack checking Don t lean the UPS when moving it out from the packaging Check the appearance to see if the UPS is damaged or not during the transportation do not switch on the UPS if any dama...

Страница 7: ...C input 2 Network Fax Modem Surge Protection option 3 Input circuit breaker 4 EPO option 5 USB communication port option 6 RS 232 communication port 7 SNMP intelligent slot option 8 Output receptacles...

Страница 8: ...k b Suggest using AWG14 or 2 1mm2 power cords for 3KVA 200 208 220 230 240VAC models c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small c...

Страница 9: ...on ON Button Turn on the UPS Press and hold ON button for at least 2 seconds to turn on the UPS Down key Press this button to display next selection in UPS setting mode Exit setting mode Press this bu...

Страница 10: ...ds to disable or enable the alarm system But it s not applied to the situations when warnings or errors occur Switch to UPS self test mode Press and hold this button for 2 seconds to enter UPS self te...

Страница 11: ...9 03 Output voltage 04 Load 05 Temperature EnvironmentTemperatu re 06 Firmware Version UPS model...

Страница 12: ...ional status and mode 08 Alarm Code Warming Message All alarm codes are present when abnormal behavior s occur s 09 The charging status can also be shown on the screen as below while the charger is on...

Страница 13: ...ages Item Settings Content Displayed 01 Mode setting Press Func button to change the setting ECO or NOR orCF Press UP button to select the previous setting Press DOWN button to select the next setting...

Страница 14: ...on to select the previous setting Press DOWN button to select the next setting 06 Bypass voltage upper limit setting Press Func button to change the setting The bypass voltage upper limit range is 230...

Страница 15: ...ble AC power to output The UPS will also charge the battery at online mode Inverter led light ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass volt...

Страница 16: ...t 18 Soft start failed Beep continuously Fault LED lit 19 UPS Inside Over Temperature Twice per second Fault LED lit 20 Heatsink Over Temperature Twice per second Fault LED lit 26 Battery over voltage...

Страница 17: ...is overload Remove excess loads from UPS output Alarm code is shown as 29 and FAULT led light The UPS shut down automatically because short circuit occurs on the UPS output Check output wiring and if...

Страница 18: ...n addition to the features of a standard NetAgent Mini NetAgent II has the option to add Net Feeler Lite to detect temperature humidity smoke andsecurity sensors Thus making NetAgent II aversatile man...

Страница 19: ...ns definition of connecting terminal on the board Relaycard electrical parameter max Type Relaycardcontact Max Switched Voltage AC 120V DC 24V AC 120V DC 5 12V Max Switched Current AC 1A DC 1A AC 1A D...

Страница 20: ...ltage point 230 264 setting the high voltage point in LCD from 230Vac to 264Vac Default 264Vac Bypass low voltage point 170 220 setting the low voltage point in LCD from 170Vac to 220Vac Default 170Va...

Страница 21: ...fter 5 seconds when the utility is normal 130 UPS transfer to bypass immediately when the utility is normal Short Circuit Hold Whole System Overheat Line Mode Switch to Bypass Backup Mode Shut down UP...

Отзывы: