Installation and Operation Manual 51
Table 9.2 Grid Specification(3W+N+PE/LN)
Grid
specification
Output Voltage
Range(Vac)
Output Frequency
Range (Hz)
Boot wait
time (S)
Error recovery
time (S)
China
187 - 252
48 - 50.5
60
60
Germany
196 - 264
47.5 - 51.5
60
60
Australia
200 - 270
48 - 52
60
60
Italy
184 - 276
49.7 - 50.3
60
60
Spain
196 - 253
48 - 50.5
180
60
U.K.
184 - 264
47 - 52
180
60
Hungary
198 - 253
49.8 – 50.2
300
60
Belgium
184 - 264
47.5 - 51.5
60
60
AUS-W
200 - 270
47.5 - 50.5
60
60
Greece
184 - 264
49.5 - 50.5
180
60
France
184 - 264
47.5 - 50.4
60
60
Metro
200 - 240
49 - 51
60
60
Thailand
198 - 242
48 - 51
60
60
GB19964
184 - 276
48 - 52
60
60
Local
184 - 276
45 - 55
60
60
60Hz
184 - 276
58 - 62
60
60
Table 9.3 Grid Specification(3W+PE/LL)
Grid
specification
Output Voltage
Range(Vac)
Output Frequency
Range (Hz)
Boot wait
time (S)
Error recovery
time (S)
China
340 - 480
48 - 50.5
60
60
Germany
340 - 460
47.5 - 51.5
60
60
Australia
340 - 480
48 - 52
60
60
Italy
320 - 480
49.7 - 50.3
60
60
Spain
340 - 440
48 - 50.5
180
60
U.K.
320 - 460
47 - 52
180
60
Hungary
360 - 440
49.8 – 50.2
300
60
Belgium
320 - 460
47.5 - 51.5
60
60
AUS-W
340 - 480
47.5 - 50.5
60
60
Greece
320 - 460
49.5 - 50.5
180
60
France
320 - 460
47.5 - 50.4
60
60
Metro
346 - 416
49 - 51
60
60
Thailand
342 - 418
48 - 51
60
60
GB19964
320 - 480
48 - 52
60
60
Local
320 - 480
45 - 55
60
60
60Hz
320 - 480
58 - 62
60
60
In the running process, errors such as AC overvoltage, AC
undervoltage, AC overfrequency and AC underfrequency occur, the