Installation and Operation Manual 14
Lightning protection
device warning
W21
Alarm message for Lightning protection device action
5.5 Type of system fault and trouble shooting
Table 5.3 Type of system fault and trouble shooting
Trouble Shooting
Alarm Message
Solution
System
Faulty
Or
Failure
Type
AC voltage &
frequency are too
high or too low
(F00-F03)
(1)Pease check mains voltage whether it is complied with local
safety standard.
(2)Please check the AC output line is properly connected. Make
sure its output voltage to see if it is normal.
(3)Disconnect PV input and restart the inverter and check whether
fault still exists.
(4)Contact with your local distributor if the fault still exists.
Bus voltage is too
high or too low
(F04-F05)
(1)Please check the setting of input mode.
(2)Disconnect PV input and restart the inverter and check whether
fault still exists.
(3)Contact with your local distributor if the fault still exists.
Bus Voltage
Abnormal
(F06)
(1)Please check the setting of input mode.
(2)Please try to restart inverter every few minutes for several times
and check whether fault still exists.
(3)Contact with your local distributor if the fault still exists.
Insulation impedance
Fault
(F07)
(1)Disconnect PV input and restart the inverter and check whether
fault still exists.
(2)Please measure impedance of PV+/PV- to ground whether is
over than 500KΩ.
(3)Please contact your local distributor if impedance is less than
500KΩ.
Input Current High
(F08)
(1)Please check the setting of input mode
(2)Disconnect PV input and restart the inverter and check whether
fault still exists.
(3)Contact with your local distributor if the fault still exists.
Hardware Current
High
(F09)
(1)Disconnect PV input and restart the inverter after few minutes
and check whether fault still exists.
(2)Contact with your local distributor if the fault still exists.
Inverter Current High
(F10)
(1)Disconnect PV input and restart the inverter after few minutes
and check whether fault still exists.
(2)Contact with your local distributor if the fault still exists.
Inverter DC Current
high
(F11)
(1)Disconnect PV input and restart the inverter after few minutes
and check whether fault still exists.
(2)Contact with your local distributor if the fault still exists.