26
SMARTRONIC MA
VII - 2 - 2 Starting auto-calibration
Autocalibration must be carried out in the following cases:
- First time use of the positioner
- Modification of the actuator mechanical stops
- Modification of the mechanical adjustment of the operating time
- Modification of an external parameter that could affect the device positioning performance
The autocalibration procedure optimises the positioner adjustment by calculating the gains, sensitivity in dead
band for the opening and closing operations.
These parameters will be stored in case of power failure.
Opening and closing times of at least 0.5 s must be respected (see chapter IV - 2 Mechanical
adjustment of the operating time)
<OK>
>3>2>1.auto
ABORT CALIB?
<OK> or <ESC>
<ESC>
>3>2>1.auto
CALIB DONE
<OK>
>3.settings
>3>2.calib
>3>2>1.auto
>3>2>1.auto
>3>2>1.auto
2.CALIB >
<OK>
<ESC>
1.AUTO >
<OK>
<ESC>
To START
<OK> or <ESC>
<OK>
CALIB STEP X/X
<ESC> to abort
CALIB FAIL: X
<OK>
VII - 3 Operating mode
SMARTRONIC MA supports three operating modes: automatic, manual and HART.
>main menu
>3.settings
>3>1.mode
>3>1>1.auto
<OK>
<OK>
<OK>
3.SETTINGS >
1.MODE >
1.AUTO
VALID ?
<ESC>
<ESC>
<ESC>
+
-
<OK> or <ESC>
>3>1.mode
>3>1>2.manu
>3>1>2.manu
2.MANU
<OK>
VALID ?
<OK>
<+> or <->
+
<ESC>
<OK> or <ESC>
--
+
-
<ESC>
pos : 50.0 %
>3>1.mode
>3>1>3.hart
3.HART
<OK>
VALID ?
<ESC>
<OK> or <ESC>
VII - 3 - 1 Automatic mode
The SMARTRONIC MA positions the valve according to the value of the setpoint signal between 4 and 20 mA.
This is the normal operating mode of the positioner.
By default, the SMARTRONIC MA is configured according to the following values:
- Closing: 4mA,
- Opening: 20mA
For a specific setting, refer to paragraph VII - 5 - 2.
>main menu
>3.settings
>3>1.mode
>3>1>1.auto
<OK>
<OK>
<OK>
3.SETTINGS >
1.MODE >
1.AUTO
VALID ?
<ESC>
<ESC>
<ESC>
<OK> or <ESC>
Содержание SMARTRONIC MA R1310