29
SMARTRONIC MA
VII - 5 Other function of the SMARTRONIC MA positioner
VII - 5 - 1 Manual calibration
Once the first autocalibration has been carried out, the operator can access the gain, dead band (DB) and
positioning stroke values (O/C POSITION see § VII - 5 - 1 - 1).
>3>2>1.auto
CALIB DONE
<OK> or <ESC>
>main menu
>3.settings
>3>2.calib
>3>2>manu
>3>2>2>1.O/C pos
>3>2>2>1.O/C pos
<ESC>
<OK>
>3>2>2>1.O/C pos
>3>2>2>1.O/C pos
3.SETTINGS >
<OK>
2.CALIB >
<OK>
2.MANU >
<OK>
1.O/C POSITION >
<OK>
SET OPEN
<OK>
SET CLOSE
<OK>
VALID ?
<OK>
CALIB OK
<ESC>
<ESC>
<ESC>
+
-
<ESC>
<+> or <- >
<+> or <->
<OK>
<OK> or <ESC>
<OK>
<ESC>
>3>2>manu
>3>2>2>2.db
>3>2>2>2.>1.Odb
>3>2>2>2.>1.Odb
>3>2>2>1.O/C pos
2.DEAD BAND >
<OK>
1.OPEN DB
<OK>
SET OP DB
<OK>
VALID ?
CALIB FAIL:04
<ESC>
--
+
-
+
<ESC>
xxx.x %
<OK> or <ESC>
<OK>
<ESC>
<OK>
>3>2>2>2.db
>3>2>2>2. >2.Cdb
>3>2>2>2.>2, Cdb
>3>2>2>1.O/C pos
<OK>
2.CLOSE DB
SET CL DB
+
-
<OK>
VALID ?
WARNING CLK DIR
<ESC>
xxx.x %
<OK> or <ESC>
<OK>
<ESC> <OK>
>3>2>manu
>3>2>2>3.gain
>3>2>2>3>1.OG
>3>2>2>3>1.OG
3.GAIN >
<OK>
1.OPEN GAIN
<OK>
SET OP GAIN
<OK>
VALID ?
<ESC>
+
-
-
-
<ESC>
xxx.x %
<OK> or <ESC>
<ESC> <OK>
>3>2>2>3.gain
>3>2>2>3>2.CG
>3>2>2>3>2.CG
2.CLOSE GAIN
<OK>
SET CL GAIN
<OK>
VALID ?
<ESC>
xxx.x %
<OK> or <ESC>
VII - 5 - 1 - 1 Positioning stroke
This setting is used to adjust the positioner operation on the actuator mechanical stops.
Although it is carried out automatically during autocalibration, this parameter can be adjusted
manually.
Once the O/C POSITION has been validated (by pressing <OK>), the mechanical
stop adjustment procedure starts:
>3>2>2>1.O/C pos
SET OPEN
<+> or <->
>3>2>2>1.O/C pos
SET CLOSE
<+> or <->
Open the valve (by pressing <+> or <->) up to the opening mechanical stop.
Then validate (<OK>)
Close the valve (by pressing <+> or <->) up to the closing mechanical stop.
Then validate (<OK>)
The difference between the two extreme positions must be greater than 45
°
.
If the positioner detects a difference between the closing direction (clockwise or counterclockwise)
configured during the previous autocalibration and the operations carried out during this manual
procedure, a warning will be displayed indicating that the closing direction has been changed.