3
COMMISSIONING / OPERATION
22
VFC 200
www.krohne.com
06/2019 - 4005059401 - AD VFC200 PB-PA R01 en
63
3
F
–
Sensor
Sensor is defective and not able to measure. Related output
values are invalid. Typically a repair or replacement of the device
is required. Check sensor / cabling /
4
- restart the device
–
if the
error still occur send back the device to the manufacturer with an
indication of the error.
64
3
M
–
Process
Process related problem(s) detected. But still the measurement
values are accurate. The output values are still valid, but this may
change in the near future. Check problem(s) /
5
- if the
problem(s) cannot be fixed contact the service department of the
manufacturer with an indication of the problem(s).
65
3
M
–
Configuration
Configuration related problem(s) detected. But still the
measurement values are accurate. The output values are still
valid, but this may change in the near future. Check problem(s) /
5
- if the problem(s) cannot be fixed contact the service
department of the manufacturer with an indication of the
problem(s).
66
3
M
–
Electronics
Converter electronic related problem(s) detected. But still the
measurement values are accurate. The output values are still
valid, but this may change in the near future. Check problem(s) /
5
- if the problem(s) cannot be fixed contact the service
department of the manufacturer with an indication of the
problem(s).
67
3
M
–
Sensor
Sensor related problem(s) detected. But still the measurement
values are accurate. The output values are still valid, but this may
change in the near future. Check problem(s) /
5
- if the
problem(s) cannot be fixed contact the service department of the
manufacturer with an indication of the problem(s).
68
3
S
–
Process
Process related fault(s) detected. E.g. the device may be operated
outside its specified operating range. The measurement accuracy
may be reduced. But still the measurement value follows the
source. Check fault(s) detected /
4
- if the fault(s) cannot be
cleared contact the service department of the manufacturer with
an indication of the problem(s).
69
3
S
–
Configuration
Configuration related fault(s) detected. E.g. the device may be
operated outside its specified operating range. The measurement
accuracy may be reduced. But still the measurement value
follows the source. Check fault(s) detected /
4
- if the fault(s)
cannot be cleared contact the service department of the
manufacturer with an indication of the problem(s).
70
3
S
–
Electronics
Converter electronic related fault(s) detected. E.g. the device may
be operated outside its specified operating range. The
measurement accuracy may be reduced. But still the
measurement value follows the source. Check fault(s) detected /
4
- if the fault(s) cannot be cleared contact the service
department of the manufacturer with an indication of the
problem(s).
71
3
S
–
Sensor
Sensor related fault(s) detected. E.g. the device may be operated
outside its specified operating range. The measurement accuracy
may be reduced. But still the measurement value follows the
source. Check fault(s) detected /
4
- if the fault(s) cannot be
cleared contact the service department of the manufacturer with
an indication of the problem(s).
72
9
Config. - Process
73
9
Config. - Initial
74
9
Config. - High Flow
75
9
Config. - Low Flow
76
9
Config. - Power Failure
Bit Number
Supported
De
sc
ription
Remedy