COMMISSIONING / OPERATION
3
17
VFC 200
www.krohne.com
06/2019 - 4005059401 - AD VFC200 PB-PA R01 en
Classic Status
Classic Status
Classic Status
Classic Status
The "Classic Status" is implemented to provide compatibility to systems which are not
configured for "Condensed Status". The coding is shown in the following table:
Quality
Quality substatus
Limits
Gr
Gr
QS
QS
QS
QS
Qu
Qu
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
0
= bad
0
1
= uncertain
1
0
= good (Non Cascade)
1
1
= good (Cascade) - not supported
Table 3-7: Coding for "Classic Status"
Quality
Quality substatus
Limits
Gr
Gr
QS
QS
QS
QS
Qu
Qu
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
0
0
0
0
0
= non-specific
0
0
0
0
0
1
= configuration error
0
0
0
0
1
0
= not connected
0
0
0
0
1
1
= device failure
0
0
0
1
0
0
= sensor failure
0
0
0
1
0
1
= no communication (last usable value)
0
0
0
1
1
0
= no communication (no usable value)
0
0
0
1
1
1
= out of service
Table 3-8: Coding for "Status = bad"
Quality
Quality substatus
Limits
Gr
Gr
QS
QS
QS
QS
Qu
Qu
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
1
0
0
0
0
= non-specific
0
1
0
0
0
1
= last usable value
0
1
0
0
1
0
= substitute-set
0
1
0
0
1
1
= initial value
0
1
0
1
0
0
= sensor conversion not accurate
0
1
0
1
0
1
= engineering unit violation (unit not in the valid set)
0
1
0
1
1
0
= sub-normal
0
1
0
1
1
1
= configuration error
0
1
1
0
0
0
= simulated value
Table 3-9: Coding for "Status = uncertain"