Before you start to connect the power supply cables, note the following drawing with the function
of the terminals:
Figure 4-3: Connecting power supply
1
Live (L)
2
Neutral (N)
3
Protective earth (PE)
INFORMATION!
All cables must have a test voltage of min. 2 kV and an appropriate outer insulation (additional to
the insulation of the individual wire). The outer insulation should be removed 40 mm / 1.57". The
minimum cross section of the wires is 1.5 mm
2
/ 16 AWG and the maximum is 2.5 mm
2
/ 12 AWG.
INFORMATION!
In order to assure proper sealing of the cable feedthrough only cables with a diameter between
6...12 mm / 0.24...0.47 inch should be used.
INFORMATION!
The device contains an internal fuse (1.6 A slow blow). Replacement of the fuse should only be
carried out by a service technician.