4
ELECTRICAL CONNECTIONS
42
IFC 300
www.krohne.com
06/2009 - 4000069802 - MA IFC 300 R03 en
4.5.2 Connecting the signal and field current cables, wall-mounted housing
•
The outer shield of signal cable A and/or B is connected via the stranded drain wire.
•
If a shielded field current cable is used, the shield must NOT
NOT
NOT
NOT be connected to the device.
•
Bending radius:
≥
50 mm / 2"
1
Open the housing cover.
2
Pass the prepared signal cable through the cable entry and connect the corresponding strand-
ed drain wires and conductors.
3
Connect the stranded drain wire of the outer shield.
4
Pass the prepared field current cable through the cable entry and connect the corresponding
conductor.
Any shield that is present must NOT
NOT
NOT
NOT be connected.
5
Tighten the screw connections of the cable entry and close the housing cover.
Figure 4-14: Electrical connection of the signal and field current cables, wall-mounted housing
INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.
.book Page 42 Wednesday, June 10, 2009 4:20 PM