OPERATION
6
111
IFC 300
www.krohne.com
06/2009 - 4000069802 - MA IFC 300 R03 en
6.3.4 Set free units
C5.8 HART
C5.8
HART
C5.8.1
HART
Switch HART
®
communication on/off::
Select:
HART on (HART
®
activated) current = 4
…
20 mA / HART off (HART
®
not
activated) current = 0
…
20 mA
C5.8.2
address
Set address for HART
®
operation:
Select: 00 (point-to-point operation, current output has normal function,
current = 4
…
20 mA) / 01...15 (multidrop operation, current output has a
constant setting of 4 mA)
C5.8.3
message
Set required text:
A
…
Z ; a
…
z ; 0
…
9 ; / - + , .*
C5.8.4
description
Set required text:
A
…
Z ; a
…
z ; 0
…
9 ; / - + , .*
C5.9 quick setup
C5.9
quick setup
Activate quick access in quick setup menu:
Select: yes (switched on) / no (switched off)
C5.9.1
reset counter 1
Reset counter 1 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.2
reset counter 2
Reset counter 2 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.3
reset counter 3
Reset counter 3 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.4
process input
Select: yes (activated) / no (switched off);
only if current input available.
Free units
Sequences to set texts and factors
Texts
Texts
Texts
Texts
Volume flow, mass flow and density:
3 digits before and after the slash
xxx/xxx (max. 3 digits before / after the slash)
Volume, mass
xxx (max. 3 digits)
Permissible characters:
A
…
Z; a
…
z; 0
…
9; / - + , . *; @ $ % ~ () [] _
Conversion factors
Conversion factors
Conversion factors
Conversion factors
Desired unit
= [unit see above] * conversion factor
Conversion factor
Max. 9 digits
Shift decimal point:
↑
to the left and
↓
to the right
.book Page 111 Wednesday, June 10, 2009 4:20 PM