TECHNICAL DATA
8
137
IFC 300
www.krohne.com
06/2009 - 4000069802 - MA IFC 300 R03 en
8.5 Accuracy
Reference conditions
•
Medium: water
•
Temperature: 20
°
C / 68
°
F
•
Pressure: 1 bar / 14.5 psi
•
Inlet run:
≥
5 DN
X [m/s]: flow velocity
Y [%]: deviation from the actual measured value (mv)
1
2
3
DN [mm]
DN [inches]
Accuracy
Curve
OPTIFLUX 5300
10
…
.100
3/8
…
4
0.15% of mv + 1 mm/s
1
150...300
6...12
0.2% of mv + 1 mm/s
2
OPTIFLUX 2300 / 4300 / 6300
10
…
.1600
3/8
…
80
0.2% of mv + 1 mm/s
2
OPTIFLUX 1300
10
…
150
3/8
…
6
0.3% of mv + 2 mm/s
3
OPTIFLUX 2300 / 4300
>1600
>64
0.3% of mv + 2 mm/s
3
OPTIFLUX 4300 / 5300 / 6300
<10
<3/8
0.3% of mv + 2 mm/s
3
WATERFLUX 3300
50...600
2...24
0.2% of mv + 1 mm/s
2
.book Page 137 Wednesday, June 10, 2009 4:20 PM