OPERATION
6
47
H250 M40
www.krohne.com
03/2020 - 4000640706 - MA H250-M40 R06 en
ERROR TIMEOUT
Data not transferred, or
transferred incorrectly
from the ESK to the
counter module.
F
Confirm menu item "1.6.3 WRITE INFO I/O".
WARNING TIMEOUT
I
LOOP CHECK
Loop check function is
active.
C
For further information refer to
ESK4A - Loop
Check Mode
on page 40.
BLOCKED FL.
Float is no longer moving,
probably blocked.
F
Execute maintenance/cleaning of device, check
application.
INT. MAG. F.
Float is missing or upside
down.
M
Check float, if installed correctly.
EXT. MAG. F.
External magnetic fields
are interfering the
measurement.
M
Avoid magnetic DC fields at installation position.
PUL. FLOW
Pulsating flow or bumping
float.
S
Check application.
NE107 AUTO CAL.
At least one auto
calibration of NE107
application diagnostic is
active. The corresponding
application diagnostic is
suppressed.
C
Deactivate auto calibration or restart device.
Table 6-9: Error messages ESK4-T
1
Category can be changed by user.
Error message
Description
Category
Remedy