Page 5
Wall Thimble
Combustion Air Kit
Pipe Section
Adjustable pipe section
IMPORTANT: Installation must comply with the vent pipe manufacturer’s installation instructions, the
requirements / restrictions as outlined in this installation manual and local building codes.
MOBILE HOME INSTALLATIONS
The stove may be installed in a permanently located, manufactured or mobile home where not prohibited by
local codes.
The following requirements must be followed:
1. Outside combustion air for all installation types is required for proper operation of this stove.
2. Do not over fire this stove and use highly volatile fuel or combustible material in this stove.
2. WARNING: DO NOT INSTALL IN A SLEEPING ROOM.
3. CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOORS, WALLS, CEILINGS AND ROOF MUST BE MAINTAINED.
4. Permanently bolt the stove to the floor. Floor protection requirements must be followed.
5. Electrically ground the stove and pedestal to the metal chassis of the home. Use a number 18 gauge or
larger copper wire.
6. Maintain an effective vapor barrier at location where ‘L’ vent exits the structure.
7. Check local codes for additional requirements / restrictions concerning mobile home installations.
8. ‘L’ Vent must be used for exhaust venting. (Single wall vent is not allowed.) Follow ‘L’ Vent manufacturer’s
installation directions and observe all listed clearances to combustibles.
Содержание OLV-PC OLIVIA
Страница 18: ......