Page 2
‚
All joints for connector pipe shall be required to be fastened with at least (3) screws. If vented
horizontally, joints shall be made gas tight using high temp sealant, RTV, or metal tape at each joint.
‚
A clean out ‘tee’ must be installed directly to the stove and at the bottom of each vertical run of the
vent (exhaust) system. The tees will provide easy access for cleaning the vent system. Single or
double
clean-out tee may be used. THE EXHAUST SYSTEM MUST BE INSTALLED SO THE ENTIRE SYSTEM MAY
BE CLEANED WITHOUT DISASSEMBLY.
‚
CANADIAN INSTALLATIONS: CAUTION: DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
‚
CANADIAN INSTALLATIONS: Where passage through a wall or partition of combustible construction is
desired, the installation shall conform to CAN/CSA-B365.
‚
CAUTION: DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE
OIL.
‚
Inspect and clean exhaust venting system frequently.
‚
It is recommended that the vent system be installed with a minimum vertical rise of 3 feet above the
stove exhaust connection.
Failure to provide adequate natural draft (vertical rise) may result in smoke being released into the
house when electricity to the stove is interrupted while burning or smoldering corn remains in the burn
pot.
‚
Increasing the vertical exhaust system is recommended when: Using more than (1) elbow or tee
Horizontal run is over (3) feet.
‚
Horizontal terminations: The exhaust pipe must be terminated by a listed end cap or a ‘L’ vent elbow
(45 or 90 degree). End caps or elbows must vent exhaust gases away from the building.
‚
Terminations above the roof line require a rain cap.
APPROVED VENTING COMPONENTS:
This stove has been tested and approved for use with the Type ‘L’ Simpson Dura-Vent Corn vent system
and Selkirk Metalbestos Direct-Temp direct vent system. Alternate brands may be used provided they
are approved by a certified testing agency as a Type ‘L’ system.
Simpson Dura-Vent Pellet vent system components:
Stove pipe adaptor
& adapter/increaser
Single Tee with Clean-out Tee Cap - Double Tee with Clean-out cap
Creates 90
o
offset with clean-out access. Allows clean-out access for horizontal
and vertical installations.
Содержание OLV-PC OLIVIA
Страница 18: ......