background image

 

COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS                       

 

NOTE:  The  following  requirements  reference 
various  Massachusetts  and  national  codes  not 
contained in this manual. 

For all sidewall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 
including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than (7) feet above finished grade in the 
area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:  

INSTALLATION OF CARBON MONOXIDE DETECTORS 

At the time of installation of the side wall horizontally vented gas fueled equipment, the installing plumber or gas-fitter shall observe that a hard wired 
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the in-
stalling plumber or gas-fitter shall observe that a battery operated or hard wired carbon monoxide detector is installed on each additional level of the dwell-
ing, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the 
services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.  
 
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or attic, the hard wired carbon monoxide detector with 
alarm and battery back-up may be installed on the next adjacent floor level. 
 
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) 
days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with 
an alarm shall be installed. 

APPROVED CARBON MONOXIDE DETECTORS 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS 
certified. 

SIGNAGE 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum of eight (8) feet above grade directly in 
line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print no less the one-half 

inch (1/2”) in size, 

 “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

  

INSPECTION 

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the 
inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08 (2) (a) 1 through 4. 

EXEMPTIONS 

The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 through 4:The equipment listed in Chapter 10 entitled “Equipmen

t Not Required To Be 

Vented” in the most current edition of NFPA 54 as adopted by the Board; and Product Approved side wall horizontally vented ga

s fueled equipment in-

stalled in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED 

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system compo-
nents with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 
  
 

Detailed instructions for the installation of the venting system design or the venting system components; and 

 
 

A complete parts list for the venting system design or venting system. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM  NOT PROVIDED 

When the manufacturer of Product Approved side wall horizontally vented gas equipment does not provide the parts for venting the flue gases, but identi-

fies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

 

 
 

The referenced “special venting systems” instructions shall be included with the appliance or equipment installation instruct

ions and;   

 
 

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a pa

rts list and  

 

detailed installation instructions. 

 
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists 
for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. 
 

PAGE 4 

Содержание Jackson XL

Страница 1: ...e information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance is only for use with the type s of ga...

Страница 2: ......

Страница 3: ...allation 10 Install the Vent System 11 12 Position the Insert Secure the Air Duct 13 Replace the Baffle 13 Secure Masonry Side Panels to Fireplace front 14 Replace the Millivolt Board 14 Attach The Sh...

Страница 4: ......

Страница 5: ...ourselves in being dedicated to not only function and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from you...

Страница 6: ......

Страница 7: ...the appliance should be located out of traffic and away from furniture and draperies The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance...

Страница 8: ...eet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in size...

Страница 9: ...ith the firebrick and smoke baffle REMOVED must be at least Height 23 1 2 Front Width 331 2 Depth 16 1 2 Width at minimum depth location 23 1 2 4 The height the of existing chimney must be a minimum o...

Страница 10: ...s Includes 12 ft compressed expandable to 25 ft co linear 3 x 4 flexible chimney and termination cap If your existing chimney is higher than 25 ft above the fireplace an extension kit Part 510 must be...

Страница 11: ...building codes This unit is equipped with a 3 8 flexible gas line connection 18 long CAUTION The manual shut off valve and millivolt board flexible gas line must not extend outside the unit cavity Se...

Страница 12: ...age 26 for checking these pressures NATURAL GAS The minimum inlet gas supply pressure 5 0 in W C Recommended inlet gas supply pressure 7 0 in W C The maximum inlet gas supply pressure 10 5 in W C Mani...

Страница 13: ...ift it up and off the studs and remove from the fireplace IMPORTANT BE CAREFUL NOT TO DAMAGE THE GASKET UNDER THE BOARD Figure C 3 NOTE The millivolt board is secured with 2 nuts at the factory After...

Страница 14: ...the front later in this manual Figure D 1 RESTRICTOR INSTALLATION The restrictor plate included in the fireplace components packet may be installed as either a large or small restrictor depending on...

Страница 15: ...ovided Apply additional sealant around the joint to ensure a seal C If an extension kit is being used it must be connected as follows Exhaust extension Apply a liberal bead of sealant provided around...

Страница 16: ...ant around the joint to ensure an air tight seal C Apply a liberal bead of sealant provided around the 3 collar on the air duct Slide the 3 combustion intake pipe over the collar and secure with screw...

Страница 17: ...E 1 below 3 Position the air duct to the fireplace by aligning the two holes in the fireplace top to the studs on each side of the 4 exhaust duct 4 Locate the baffle with the seasonal heat dump inside...

Страница 18: ...bottom of the millivolt board Figure G 1 4 Install the pilot shield over the pilot assembly Figure G 2 5 Connect the flexible gas line to the manual shut off valve 6 Connect any remote control wall s...

Страница 19: ...positioning in one of the three mounting holes 2 Secure the right and left shroud pieces to the top piece by aligning the 2 holes in the side pieces to the holes in the top piece Secure with the phil...

Страница 20: ...the 2 holes in the side pieces to the holes in the top piece Secure with the screws provided 2 ea side B NOTE Screws are secured from the bottom 3 Snap the rocker switch in place on the shroud Figure...

Страница 21: ...he screws A 2 ea side securing the masonry panels Figure H 6A Cut lower end of each tab at the location shown Figure H 4 Note flange orientation 5 Align the holes in the right mounting bracket to the...

Страница 22: ...place behind the lower grill to re position this speed control box to the left side if desired 1 Attach the limit switch on the left side of the millivolt board under the firebox 2 Plug fan cord into...

Страница 23: ...rate extensions The X7 X9 logs when properly installed set on the burner cover not on klinkers 3 Brush Rock wool embers onto burner and base logs with a stiff bristle brush NOTE You will not use all t...

Страница 24: ...O NOT ATTEMPT TO ADJUST THE HEAT DUMP OPENING IF THE FIREPLACE HAS BEEN IN OPERATION ALLOW AMPLE TIME TO COOL OR USE THE APPROPRIATE PROTECTION TO AVOID SERIOUS BURNS AND OR PROPERTY DAMAGE A Remove t...

Страница 25: ...be placed over the remote receiver to prevent overheating Remote Control Wiring Diagram Thermostat Wiring Diagram THERMOSTAT WALL SWITCH REMOTE PAGE 21 CAUTION DO NOT CONNECT HIGH VOLTAGE 115V WIRE TO...

Страница 26: ...ANCE DUE TO HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion...

Страница 27: ...ety information on the front cover and on the previous page of this installa tion manual If you don t smell gas go to the next step B Locate pilot follow metal tube from gas control The pilot is locat...

Страница 28: ...ff wall switch or adjust setting on the thermostat or remote control NOTE The pilot will stay lit H Turn the pilot off by pushing in and turning the gas control knob to the OFF position DO NOT FORCE T...

Страница 29: ...er switch to OFF 7 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten 8 Attach manometer to manifold pressure tap to verify that it is completely sealed Man...

Страница 30: ...ts Tighten nuts only enough to secure baffle Baffle must be allowed to float as the fireplace heats and cools 7 Replace the logs and glass ANY SAFETY SCREEN OR GUARD REMOVED FOR SERVIC ING MUST BE REP...

Страница 31: ...NSTRUCTIONS A Check that pilot flame impinges on thermocouple Clean and or adjust pilot for maximum flame impingement B Ensure the thermocouple connection at gas valve is fully inserted and tight hand...

Страница 32: ...ts wires are faulty or connections are bad TROUBLESHOOTING BURNER WILL NOT LIGHT FREQUENT PILOT OUTAGES A Pilot shield not installed B Pilot flame too high or too low causing pilot safety to drop out...

Страница 33: ...e Pilot Tubing Valve to Pilot OCK S50A LP Gas Conversion Kit 9XL 135 Burner Tube Cover Consult your dealer for information on optional accessories available for this fireplace This appliance tested ce...

Страница 34: ......

Страница 35: ...PAGE 30...

Страница 36: ......

Страница 37: ...PAGE 31...

Отзывы: