NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure
testing of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any
pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
IMPORTANT NOTICE:
Pressure check taps for the manifold (outgoing) and inlet (incoming) pressure have been incorporated into the
valve. The pressure tap marked „OUT‟ measures outgoing pressure and the pressure tap marked „IN‟ measures incoming pressure. Follow
instructions below for proper testing procedures.
MANIFOLD PRESSURE TEST:
1. Light pilot.
2.
Loosen manifold („OUT‟) pressure tap screw (counter
-clockwise).
3.
Attach manometer to pressure tap using a 5/16” I.D. hose.
4.
Turn gas control knob to „ON‟.
5.
Press rocker switch to „ON‟ and note manometer reading.
6.
Press rocker switch to „OFF‟.
7. Disconnect manometer hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
8. Attach manometer to manifold pressure tap to verify that it is completely sealed. Manometer should read no pressure when the
rocker switch is pressed to „ON‟.
INLET PRESSURE TEST:
1.
Loosen inlet („IN‟) pressure tap screw (counter
-clockwise).
2.
Attach manometer using a 5/16” I.D. hose.
3. Light pilot.
4.
Turn gas control knob to „ON‟ (burner should not light). Note manometer reading.
5.
Press rocker switch to „ON‟. Check pressure to ensure that it stays near the maximum inlet pressure.
6.
Press rocker switch to „OFF‟.
7.
Turn gas control knob to „OFF‟.
8. Disconnect hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
9. Relight pilot and turn gas control knob to „ON‟. Reattach manometer to inlet pressure tap to verify that it is
completely sealed. Manometer should read no pressure.
CAUTION: A LOW PRESSURE READING CAN
CAUSE DELAYED IGNITION
PRESSURE TESTING
PAGE 25
NOTE: If inlet pressure reading is too high or too low, contact the gas company. Only a qualified gas service technician should adjust the
incoming gas pressure.
INLET
MANIFOLD
Содержание Jackson XL
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 34: ......
Страница 35: ...PAGE 30...
Страница 36: ......
Страница 37: ...PAGE 31...