Issue
Cause
Solution
Pilot and burner
extinguish while in
operation
No LP gas in tank
Check LP (propane) tank. Refill if necessary.
Incorrect glass assembly
installation
Refer to 7.1 Glass Assembly, on page 17.
Incorrect vent cap installation
Adjust if necessary
Vent cap blockage
Remove debris if necessary
Inner vent pipe leaking exhaust
gases back into the firebox
Check for leaks and repair if necessary.
Excessive draft
An exhaust restrictor may be necessary into the exhaust pipe outlet of
the fireplace.
Soot appears on glass
Improper log placement
Refer to Section 7.2, #CK34-500 Log Set Installation on page 18.
Improper venturi setting
Venturi may need to be opened slightly to allow more air into the gas mix.
Refer to10.2 Burner Tube Venturi Adjustment, on page 28.
Incorrect vent cap installation
Adjust if necessary
Vent cap blockage
Remove debris if necessary
Flame burns blue and
lifts off burner
Improper venturi setting
Venturi may need to be opened slightly to allow more air into the gas mix.
Refer to 10.2 Burner Tube Venturi Adjustment, on page 28.
Incorrect vent cap installation
Adjust if necessary
Blockage or leakage of the
vent system.
Check the vent pipe for leaks and the vent cap for debris. Repair vent
pipe or remove debris from vent cap if necessary.
No reaction to
command
Battery pack batteries or
remote control batteries low.
Replace batteries
No communication between
remote control and IFC module
Reprogram remote control to IFC module. Refer to 9.1 Initialize the Control
System for the First Time, on page 23.
A maximum number of failed
ignitions or flame restorations
has been reached
Reset IFC module
30