Korenix JetNet 4706 Скачать руководство пользователя страница 16

 

JetNet 4706/4706f Industrial Managed PoE Switch   

12

 

10.  Once you enter the web-based management interface, you can change the 

JetNet 

4706/4706f

’s IP address to fit your network environment. 

 

Note 1

: Internet Explorer Version 5.0 or later does not allow Java applets to open 

sockets by default. Users must directly modify the browser settings to selectively enable 
Java applets in order to use network ports. 

Note 2

: The Web UI connection session of 

JetNet 4706/4706f

 will logout automatically if 

you do not input anything after 30 seconds. Re-login if this occurs. 

 

 

3.2.2 Secured 

Web 

Interface 

 

The

 Korenix

 web management page also provides a secure HTTPS login. All the 

configuration commands will be secure, making it hard for hackers to figure out login 
password and configuration commands.   

1. 

Launch a web browser (Internet Explorer or Mozilla FireFox) on your PC. 

2. Type 

https://192.168.10.1

 (or the IP address of the switch) into the web address 

window. Press 

Enter

3. 

A popup screen will appear and request you to trust the secure HTTPS connection 
distributed by 

JetNet 4706/4706f

. Press 

Yes

4. 

The login screen will appear next. 

5. 

Key in the username and password. The default username and password are 

admin

6. Click 

OK.

 The welcome page of the web-based management interface will now 

appear. 

 

 

 

 

Содержание JetNet 4706

Страница 1: ...JetNet 4706 4706f Industrial Managed PoE Switch 1 Korenix JetNet 4706 4706f Industrial Managed PoE Switch User Manual Version 2 11 20 DEC 2010 www korenix com...

Страница 2: ...d PoE Switch 2 Korenix JetNet 4706 4706f Industrial Managed PoE Switch User Manual Copyright Notice Copyright 2008 Korenix Technology Co Ltd All rights reserved Reproduction in any form or by any mean...

Страница 3: ...rcial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio c...

Страница 4: ...reparation for Serial Console 10 3 2 Preparation for Web Interface 11 3 3 Preparation for Telnet Console 13 4 Feature Configuration 16 4 1 Command Line Interface CLI Introduction 17 4 2 Basic Settings...

Страница 5: ...ms backup time when the main path is disconnected and also integrates the 2004 edition of IEEE 802 1d standard for Rapid Spanning Tree protocol including STP function To obtain superior transmission p...

Страница 6: ...d Multiple Super Ring technology MSRTM up to 5ms recovery time Patented Rapid Dual Homing RDHTM technology SNMP v1 v2c v3 IGMP snooping v1 v2 v3 RMON VLAN QoS Network security by IP MAC address SSL an...

Страница 7: ...2 Wiring Power Inputs 2 3 Wiring Digital Input 2 4 Wiring Relay Output 2 5 Wiring Fast Ethernet Ports 2 6 Wiring Combo Ports 2 7 Wiring RS 232 console cable and pin assignment 2 8 DIN Rail Mounting In...

Страница 8: ...s please check the following figure Mylar Layout Port Layout JetNet 4706 4706f includes 4 Port 10 100TX with embedded PoE injector function in ports 1 4 the PoE ports can deliver a maximum of 100w in...

Страница 9: ...mp screws to prevent DC wires from becoming loose 4 Power 1 and Power 2 support power redundancy and polarity reverse protection functions 5 Positive and negative power system inputs are both accepted...

Страница 10: ...ectric shock we suggest making a direct connection between the JetNet 4706 4706f and earth ground to avoid system damage 1 On the right side of the JetNet 4706 4706f there is one earth ground screw 2...

Страница 11: ...100m 328 ft apart The wiring cable types are as follows 10Base T 2 pair UTP STP Cat 3 5e 6 cable EIA TIA 568 B 2 100 ohm up to 100m 100Base TX 2 pair UTP STP Cat 5e 6 cable EIA TIA 568 B 2 100 ohm up...

Страница 12: ...e ensure the PD pin assignment follows the IEEE 802 3af PD standards There are some IEEE 802 3af pre standard PDs that only accept mode A for power IEEE 802 3af indicates that the PD should be powered...

Страница 13: ...IN Rail set is missing please contact a Korenix distributor for help 2 9 Wall Mount Installation Follow the steps below to install the JetNet 4706 4706f wall mount plate Use the hook holes located at...

Страница 14: ...covered in this chapter 3 1 Preparation for Serial Console 3 2 Preparation for Web Interface 3 3 Preparation for Telnet console 3 1 Preparation for Serial Console In the JetNet 4706 4706f package Kor...

Страница 15: ...k can access the switch via Web browser 1 Verify that your network interface card NIC is operational and that your operating system supports TCP IP protocol 2 Wire the DC power to the switch and conne...

Страница 16: ...ogin if this occurs 3 2 2 Secured Web Interface The Korenix web management page also provides a secure HTTPS login All the configuration commands will be secure making it hard for hackers to figure ou...

Страница 17: ...3 3 2 SSH Secure Shell The Korenix JetNet 4706 4706f also supports SSH You can remotely connect to the switch by command line interface The SSH connection can secure all the configuration commands you...

Страница 18: ...nfiguration enter the Host Name IP Address of your JetNet 4706 4706f and Port number default 22 Choose the SSH protocol Then click on Open to start the SSH session console 2 After clicking on Open you...

Страница 19: ...tNet 4706 4706f will open 4 Type in the login name and password The default login name and password are admin 5 All the commands you see in SSH are the same as the CLI commands you see via RS232 conso...

Страница 20: ...res The following topics are covered in this chapter 4 1 Command Line Interface CLI Introduction 4 2 Basic Settings 4 3 Port Configuration 4 4 Power over Ethernet 4 5 Network Redundancy 4 6 VLAN 4 7 T...

Страница 21: ...onfiguration and enter the global configuration mode You can type configure terminal to enter the next mode or exit to leave to see a list of available command by types Following diagram shows the com...

Страница 22: ...want to enter a specific interface configuration mode You can type exit to leave or for a list of available commands Switch configure terminal Switch config access list Add an access list entry admini...

Страница 23: ...e a command or set its defaults quit Exit current mode and down to previous mode shutdown Shutdown the selected interface Switch config interface fa2 Switch config if auto negotiation Enables auto neg...

Страница 24: ...t Mode Type configure terminal to enter global configuration command Switch Global configuration In global configuration mode you can configure all the features that the system provides Enter Type con...

Страница 25: ...Stops an unfinished command Ctrl S Locks the screen of the terminal You will not be able to input a command Ctrl Q Unlocks a locked screen Ctrl Z Exits configuration mode An alert message appears whe...

Страница 26: ...n reload the system to factory default and reboot the system The following is included in this section 4 2 1 Switch Setting 4 2 2 Admin Password 4 2 3 IP Configuration 4 2 4 Time Setting 4 2 5 DHCP Se...

Страница 27: ...ription View a description of the system JetNet 4706 4706f Industrial Management Ethernet Switch is the name of this device Firmware Version Display the firmware version installed on this device MAC A...

Страница 28: ...e IP address reserved by your network for your JetNet If DHCP Client function is enabled you don t need to assign an IP address as it will be overwritten by the DHCP server The default IP address is 1...

Страница 29: ...s here to synchronize the clocks of several switches on the network JetNet4706 4706f also provides Daylight Saving function Manual Setting User can select Manual setting to change time as user want an...

Страница 30: ...03 00 Brasilia 20 GMT 03 00 Buenos Aires Georgetown 21 GMT 03 00 Greenland 22 GMT 02 00 Mid Atlantic 23 GMT 01 00 Azores 24 GMT 01 00 Cape Verde Is 25 GMT Casablanca Monrovia 26 GMT Greenwich Mean Ti...

Страница 31: ...resby 69 GMT 10 00 Hobart 70 GMT 10 00 Vladivostok 71 GMT 11 00 Magadan Solomon Is New Caledonia 72 GMT 12 00 Aukland Wellington 73 GMT 12 00 Fiji Kamchatka Marshall Is 74 GMT 13 00 Nuku alofa Dayligh...

Страница 32: ...not be assigned to the network device Add or remove an IP address from the Excluded Address List by clicking the Add or Remove button Manual Binding JetNet 4706 4706f provides a MAC address and IP ad...

Страница 33: ...files saved in the switch s flash to the admin PC or TFTP server This will allow you to go to the Restore command later in order to restore the configuration file back to the switch Before you restor...

Страница 34: ...txt files modify the file add remove configuration settings and then restore it back on to the switch Startup Configuration File After you have saved the running config to flash the new settings will...

Страница 35: ...update the switch with the latest firmware Korenix provides the latest firmware on their Web site www korenix com New firmware may include new features bug fixes or other software changes The Web site...

Страница 36: ...ou do so make sure that your TFTP server is ready Then type in the TFTP Server IP address This mode can be used in both Web UI and CLI TFTP Server IP Address Key in the IP address of your TFTP Server...

Страница 37: ...ll reset all configurations except the IP address to its default settings The system will show you a popup message window after running this command Default settings will be in effect after rebooting...

Страница 38: ...ill connect to the switch via the network 4 2 9 System Reboot System Reboot allows you to reboot the device Some of the feature changes require you to reboot the system Click the Reboot button to rebo...

Страница 39: ...Password User Name and Password Switch config administrator NAME Administrator account name Switch config administrator admin Command incomplete Switch config administrator orwell PASSWORD Administra...

Страница 40: ...startup config tftp 192 168 10 33 Writing Configuration OK Note 1 To backup the latest startup configuration file you should save current settings to flash first You can refer to 4 12 to see how to s...

Страница 41: ...JetNet 4706 4706f Industrial Managed PoE Switch 37 Reboot Switch reboot...

Страница 42: ...configure port auto negotiation speed duplex and flow control Select the port you want to configure and make changes to the port State column Enable or disable the state of this port Once you disable...

Страница 43: ...t link to each other If both ends are in different duplex modes they will be connected by half mode 4 3 2 Port Status Port Status shows you the current port status A description of each column is as f...

Страница 44: ...erface fastethernet1 is shutdown now Switch config if no shutdown Enable port state Port1 Link Change to DOWN Port1 Link Change to UP interface fastethernet1 is up now Switch config if Port1 Link Chan...

Страница 45: ...mit all frames broadcast Limit Broadcast frames flooded unicast Limit Broadcast Multicast and flooded unicast frames multicast Limit Broadcast and Multicast frames Switch config if rate limit ingress...

Страница 46: ...mode for user configuration of the power limit to IEEE 802 3af standard PD or Ultra mode for user configuration to perform at the high power limitation The following figure shows the Web UI interface...

Страница 47: ...er the remote device The following figure shows the Web configure interface for Power over Ethernet PD Status Detection You can enable disable PD Status Detection function and type in the IP address t...

Страница 48: ...n Display the PoE status of interface Examples Switch enable Switch show poe status fa1 Interface fastethernet1 PoE Status Powering mode 802 3af Control mode User Enable Status Searching Port Type POE...

Страница 49: ...2 3 4 5 6 7 8 19 20 21 22 23 Tuesday 0 1 2 3 4 5 6 7 8 19 20 21 22 23 Wednesday 0 1 2 3 4 5 6 7 8 19 20 21 22 23 Thursday 0 1 2 3 4 5 6 7 8 19 20 21 22 23 Friday 0 1 2 3 4 5 6 7 8 19 20 21 22 23 Satu...

Страница 50: ...al ultra POWER Parameters Standard Standard 802 3af mode Manual Manual mode Ultra Ultra mode POWER 802 3af mode N A Manual mode 0 44 15 4 Ultra mode 0 44 30 Command Mode Interface mode Description Set...

Страница 51: ...t 4706 4706f supports standard RSTP Multiple Super Ring Rapid Dual Homing and Legacy Super Ring Client modes Multiple Super Ring MSR technology is Korenix s 3rd generation Ring redundancy technology T...

Страница 52: ...the evolution of STP providing for a much faster spanning tree convergence after a topology change This is specified in IEEE 802 1w In 2004 802 1w was included into the 802 1D 2004 version This switc...

Страница 53: ...before checking to see if it should be changed to a different state Once you have completed your configuration click the Apply button to apply your settings Note You must observe the following rules t...

Страница 54: ...s to form a ring or loop Typically the managed switches are connected in a series and the last switch is connected back to the first one In such a connection you can use Korenix Super Ring and Rapid S...

Страница 55: ...not be changed Name This field will show the name of the Ring If it is not filled in when creating it will be automatically named by the rule RingID Version The version of Ring can be changed here The...

Страница 56: ...l Homing port to two uplink switches In Rapid Dual Homing you don t need to configure specific port to connect to other protocol The Rapid Dual Homing will smartly choose the fastest link for primary...

Страница 57: ...id range is 1 10 seconds Switch config spanning tree hello time 2 Forward Delay Switch config spanning tree forward time 4 30 Valid range is 4 30 seconds Switch config spanning tree forward time 15 al...

Страница 58: ...nning tree ports Port State Summary Blocking Listening Learning Forwarding Disabled 0 0 0 2 8 Port Link Type Summary AutoDetected PointToPoint SharedLink EdgePort 9 0 1 9 Port Info Switch show spannin...

Страница 59: ...efault 128 valid range is 0 or 255 Switch config super ring plus port cost 100 0 255 valid range is 0 or 255 default set default 128 valid range is 0 or 255 Switch config super ring plus port cost 100...

Страница 60: ...Port fa1 fa2 Path Cost 100 200 Rapid Dual Homing Disabled Statistics Watchdog sent 0 received 0 missed 0 Link Up sent 0 received 0 Link Down sent 0 received 0 Role Transition count 0 Ring State Trans...

Страница 61: ...ation is for the JetNet 4706 4706f management interface security Only the management packet with the same VLAN ID will forward to a CPU interface You can assign an ID number from 1 to 4094 and then cl...

Страница 62: ...N table display Description CLI Command Displays the current port based vlan configuration for each port which include the default PVID the ports for forwarding and the egress mode of the port show vl...

Страница 63: ...lt PVID for this port switchport trunk native vlan VID ex assign VID 1 to port 1 Switch configure terminal Switch config interface fa1 Switch config if switchport trunk native vlan 1 Set port default...

Страница 64: ...rv information to prioritize the traffic of your industrial network The following commands are explained in this section 4 7 1 QoS Setting 4 7 2 CoS Queue Mapping 4 7 3 DSCP Queue Mapping 4 7 4 CLI Co...

Страница 65: ...o for the next command After configuring click the Apply button to enable the settings 4 7 2 CoS Queue Mapping This area is where the user can set CoS values to the Physical Queue mapping table Since...

Страница 66: ...rity wrr Weighted Round Robin Use an 8 4 2 1 weight Switch config qos queue sched sp cr Queue Scheduling WRR Switch config qos queue sched wrr Port Setting priority Default Port Priority Switch config...

Страница 67: ...st Mode Switch show qos trust QoS Port Trust Mode Port Trust Mode 1 DSCP first 2 COS only 3 COS only 4 COS only 5 COS only 6 COS only 7 COS only 8 COS only 9 COS only 10 COS only Display Port Setting...

Страница 68: ...mapping Switch show qos dscp map DSCP to Queue Mapping dscp d1 d2 d2 0 1 2 3 4 5 6 7 8 9 d1 0 1 1 1 1 1 1 1 1 0 0 1 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 1 1 1 1 1 1 3 1 1 2 2 2 2 2 2 2 2 4 2 2 2 2 2 2 2 2 3...

Страница 69: ...hat the host wants to be or is a member of a given group indicated in the report message Leave Group A message sent by a host to the querier to indicate that the host has quit as a member of a specifi...

Страница 70: ...ed PoE Switch 66 IGMP Snooping Table In the table you can see the multicast group IP address and the member ports of the multicast group The JetNet 4706 4706f supports 256 multicast groups Click the R...

Страница 71: ...means IGMP V1 General Query The query will be forwarded to all multicast groups in the VLAN V2 means IGMP V2 Specific Query The query will be forwarded to specific multicast groups Disable allows you...

Страница 72: ...tch config if ip igmp Switch config if ip igmp query interval 60 Change query interval to 60 seconds default value is 125 seconds IGMP Query Max Response Time Switch config int vlan 1 Go to management...

Страница 73: ...section 4 9 1 SNMP Configuration 4 9 2 SNMP v3 Profile 4 9 2 SNMP Traps 4 9 3 CLI Commands for SNMP 4 9 1 SNMP Configuration This allows users to configure the SNMP V1 V2c Community The community stri...

Страница 74: ...vel Here the user can select the following levels of security None User Authentication and Authentication with privacy Authentication Protocol Here the user can select either MD5 Message Digest algori...

Страница 75: ...ion You will not need to install new applications to read the notification information This page allows users to Enable SNMP Trap configure the SNMP Trap server IP Community name and trap Version V1 o...

Страница 76: ...ap host add OK SNMP Trap Server IP with version 1 and community Switch config snmp server host 192 168 10 33 version 1 private SNMP trap host add OK Note private is the community name version 1 is the...

Страница 77: ...pply your configuration 4 10 1 IP Security Add Security IP You can assign any PC as an administrator workstation by adding a PC s IP address into the Security IP field Only these IP addresses will be...

Страница 78: ...eatures include a System Log for local and remote servers SMTP E mail alerts and a Fault Relay alarm The following commands are included in this section 4 11 1 Fault Relay Setting 4 11 2 Event Selecti...

Страница 79: ...pe Dry Output On Period Sec Type in the amount of time you would like Relay Output to be on This can range from 0 4294967295 seconds Off Period Sec Type in the amount of time you would like Relay Outp...

Страница 80: ...en turned off that you would like the relay output to be turned back on How to configure After selecting the Ping Failure event type the system will change the Relay Output to short state light the al...

Страница 81: ...Selection Event Types are divided into 3 basic groups System Events Port Events and PoE Events System Events relate to the overall function of the switch whereas Port Events relate to the activity of...

Страница 82: ...ring Disable The PoE port is not powering Once you have finished configuring the settings click the Apply buttonto apply your configuration 4 11 3 SysLog Configuration System Log is useful in providin...

Страница 83: ...the settings click the Apply buttonto apply your configuration Note When enabling Local or Both modes you can monitor the system logs in Monitor and Diag Event Log page 4 11 4 SMTP Configuration The J...

Страница 84: ...ail Address 3 The third email address to receive email alert from JetNet Max 40 characters Rcpt E mail Address 4 The fourth email address to receive email alert from JetNet Max 40 characters Once you...

Страница 85: ...Switch link down event linkup Switch link up event all Switch all event authentication Authentication failure event fault relay Switch fault relay event power Switch power failure event super ring Swi...

Страница 86: ...1 korecare korenix com ok Authentication with username and password Switch config smtp server authentication username admin password admin SMTP Email Alert set authentication Username admin Password...

Страница 87: ...0 seconds The Aging Time can be modified on this page Static Unicast MAC Address For some applications users may need to type the static Unicast MAC address into its MAC address table On this page you...

Страница 88: ...at your network cable is not connected correctly or the network performance of the port is poor Please check your network cable Network Interface Card connected to your device the network application...

Страница 89: ...The entries include the index and data time and content of the occurrences Click the Clear buttonto delete the entries Click the Reload button to refresh the table 4 12 4 Ping Utility This page provid...

Страница 90: ...dress table ucast static set ok Note rule mac address table static MAC_address VLAN VID interface interface_name Add Multicast MAC address Switch config mac address table multicast 0100 5e01 0101 vlan...

Страница 91: ...od and TxGood mode Interface fastethernet1 is enable connected which has Inbound RxGood 1292 Outbound TxGood 1978 Bad Collision Mode Switch config rmon statistics counter mode error collisions Set RMO...

Страница 92: ...ve Configuration allows you to save any configuration you just made to the Flash Powering off the switch without clicking Save Configuration will cause loss of new settings After selecting Save Config...

Страница 93: ...JetNet 4706 4706f Industrial Managed PoE Switch 89...

Страница 94: ...out methods Your web connection will log out if you do not input a command for 30 seconds The Logout command allows you to manually log out the web connection Click Yes to logout and No to go back to...

Страница 95: ...Provides Over current protection by PD class Management Management interface SNMP v1 v2c and v3 Web browser JetView Pro and CLI Management Management Security 4 entries for web telnet SNMP management...

Страница 96: ...Control Each PoE port can be activated and powered scheduling with different rule It supports weekly schedule on hourly basis IP Security IP security to prevent unauthorized access Interface Number o...

Страница 97: ...class B CE EN61000 3 2 2001 Harmonic Test CE EN61000 3 3 1995 Flicker test EMS EN61000 4 2 ESD EN61000 4 3 RS EN61000 4 4 EFT EN61000 4 5 Surge EN61000 4 6 CS Shock IEC60068 2 27 Vibration IEC60068 2...

Страница 98: ...he private MIB tree is the same as the web tree This is easier to understand and use If you are not familiar with the standard MIB directly use the private MIB to manage monitor the switch there is no...

Страница 99: ...05 14 Apr 2008 1 Change RSR to MSR 2 Add description for Forced powering mode 3 Minor command error fixing V2 1 30 Apr 2008 Synchronous user s manual version to latest firmware version v2 1 V2 11 20...

Страница 100: ...apabilities with competitive production cost and quality support Global Sales Strategy Korenix s global sales strategy focuses on establishing and developing trustworthy relationships with distributor...

Отзывы: