101
Relay turn on for 5 seconds then off for 10 seconds
How to configure: Select the DI Number you want to monitor and DI State,
High or Low. For example: When DI 1 and High are selected, it means
when DI 1 is pulled high, the system will short Relay Output and light DO
LED
.
Event Type:
Dry Output
On Period (Sec):
Type the period time to turn on Relay Output. Available
range of a period is 0-4294967295 seconds.
Off Period (Sec)
: Type the period time to turn off Relay Output. Available
range of a period is 0-4294967295 seconds.
How to configure
: Type turn-on period and turn-off period when the time is
reached, the system will turn on or off the Relay Output. If you connect DO
to DI of the other terminal unit, the setting can help you to change DI state.
If you connect DO to the power set of other terminal units, this setting can
help you to turn on or off the unit.
How to turn On/Off the other device
: Type “1” into the “On period” field
and “0” into “Off Period” field and apply the setting, then it t will be trigger to
form as a close circuit.
To turn off the relay, just type “0” into the “On period” field and “1” into “Off
Period” field and apply the setting, the relay will be trigger to form as a open
circuit.
This function is also available in CLI, SNMP management interface. See
the following setting.