3. OPTIONAL FUNCTIONS
3.1. Recirculation (REC)
Extracted air recirculation function is available in units with recirculation sections. Recirculation section is intended for
mixing extracted and supplied air for heating or cooling of air flows in order to reduce energy consumption of heaters/coolers.
The recirculation damper control method is selected during ordering of the unit. Available recirculation damper control
methods:
• By air quality
When the indoor air quality is good, a recirculation damper is opened and outdoor dampers are closed. In this way, the
extracted air is returned to the supply air flow. When air quality is decreasing, the recirculation valve starts gradually closing
and more fresh air is supplied from outside. The user may also set minimum fresh air volume to be supplied even when the
indoor air quality is good.
• By schedule
The user sets a weekly schedule with times and percentage for opening the recirculation damper.
• By outdoor temperature
The user sets outdoor temperature limits at which the recirculation damper will be opened proportionally:
R
ecir
cula
ted air
, %
Winter
recirculation
stop
Winter
recirculation
start
Summer
recirculation
start
Summer
recirculation
stop
0
100
Outdoor temperature, °C
Fig. 3
REC function operation
• Control by external signal
Recirculation damper position is changed by connecting an external device (switch, motion sensor, thermostat) to the
C5 controller board, which opens or closes contacts (see “Installation Manual”). The user specifies two recirculation damper
positions (as a percentage): for open and for closed contact.
The volume of supplied and extracted air for all recirculation control methods is determined by an activated ventilation
mode (see “Ventilation modes”).
For information on how to activate this function and alter settings see Chapter “Control and Settings”.
3.2. Humidity control function (HUM)
Humidity control function is intended for maintaining the user-defined air humidity level. This function controls air hu-
midifiers or dehumidifiers according to the user-defined humidity level and also can perform dehumidification using inte-
grated heating/cooling devices. This function requires one or two humidity sensors connected to the C5 controller board
(see “Installation Manual”).
This function can be used to maintain:
• Supply air humidity level
– when a duct-mounted supply air humidity sensor is used.
• Indoor humidity level
– when two humidity sensors are used. Indoor air (or extract air) sensor measures the desired
humidity level in the premises, whereas the supplied air humidity is limited according to the readings of a duct-mounted
humidity sensor.
Settings for humidity control function and humidifier/dehumidifier control type is selected during ordering of the air
handling unit. Later, these settings may only be changed by a service representative. Humidity control function has priority
over AQC function. For information on how set a desired humidity value see Chapter “Control and Settings”.