7.2. Filters
Check if filters are not damaged, torn or dampened. Filter replacement intervals depend on the environment as well as
time of year, for example, during spring and summer filters may be contaminated with pollen, pubescence or insects, there-
fore replacement intervals are shorter. Replace filters if they are visibly dirty even though it is not time yet or differential pres-
sure has not reached a critical limit yet. Contaminated filters increase pressure loss of the unit, reduce purification efficiency
and increase electricity consumption of fans. If differential pressure sensors are installed, check them for proper operation;
check whether their pressure tubes are clean/intact.
Fig. 4
Filter clamping device
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device.
Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted,
handles are retracted and the filter clamping device presses the filters to the gaskets.
When inserting filters, make sure that their pockets are upright, filter frames are tightly seated and
gaskets are intact.
In case filters from another manufacturer or filters of other filtration class is used instead of factory-fitted filters, calibra-
tion of clean filters shall be performed after filter replacement. Filter calibration is described in chapter “Control and Settings”.