18
UAB KOMFOVENT we reserve the right to make changes without prior notice
VERSO PRO2_guide_20-07
EN
• Outdoor compensated ventilation (OCV)
Setting winter and summer outdoor temperature limits for reducing ventilation intensity.
When the outdoor temperature is within the range of “Winter compensation start” and “Summer
compensation start”, the unit operates in a selected ventilation mode.
Reset settings
Enable
Setpoint 1
1000 ppm
Setpoint 2
880 ppm
Mode 1
COMFORT 1
Mode 2
COMFORT 2
Air quality control
Reset settings
Enable
Setpoint
1000 ppm
Operation on demand
Outdoor compensated...
Reset settings
Enable
Winter stop
-15 °C
Summer start
25 °C
Winter start
5 °C
Summer stop
35 °C
Reset settings
Enable
Start when indoor
25 °C
Stop when indoor
20 °C
Summer night cooling
Reset settings
Enable
Setpoint
15 °C
Minimum temperature ...
• Air quality control (AQC)
Selecting an air quality limit up to which the air handling unit will run during the activated
mode and above which the ventilation intensity will be automatically increased. Air quality limit
is set for two different ventilation modes during which the function will be used and the desired
value will change automatically as the mode changes. If the unit operates in a different ventila-
tion mode than the one set, air quality control function will be disabled automatically.
• Operation on demand (OOD)
Setting a critical air quality sensor value. The unit starts as soon as this value is exceeded.
• Summer night cooling (SNC)
Setting two indoor temperatures for the function to start running and stop.
• Minimum temperature control (MTC)
Setting a minimum desired supply air temperature.
Содержание Verso Pro 2 Series
Страница 1: ...User Manual EN Verso Pro 2 ...