5.2.6. Operation on demand (OOD)
Setting a critical air quality sensor value. The unit starts as soon as this value is exceeded.
Enable
Setpoint
OPERATION ON DEMAND (OOD)
800
ppm
5.2.7. Recirculation control (REC)
1
Displayed function windows depend on the selected recirculation control method (see Chapter 3 “Optional Functions”):
• By air quality
Setting an indoor air quality limit up to which the extracted air is recirculated. The minimum position of the opened re-
circulation damper is also indicated, i.e. the minimum volume of fresh air to be supplied from the outside (as a percentage of
the set air volume) even when the indoor air quality is good. Air quality limit is set for two different ventilation modes during
which the function will be used and the desired value will change automatically as the mode changes. If the unit operates in
a different ventilation mode than the one set, REC function is disabled automatically.
Enable
RECIRCULATION CONTROL (REC)
ppm
600
Setpoint 1
Mode 1
Comfort1
ppm
800
Setpoint 2
Mode 2
Comfort2
%
40
Min. fresh air 1
%
20
Min. fresh air 1
• By outdoor temperature
Setting four outdoor temperature values for controlling the recirculation damper position.
Enable
RECIRCULATION CONTROL (REC)
Summer recirculation start
Winter recirculation start
Winter recirculation end
Summer recirculation end
°C
-40.0
°C
0.0
°C
20.0
°C
50.0
1
Displayed only when this function is pre-ordered.