46
UAB KOMFOVENT we reserve the right to make changes without prior notice
VERSO PRO2_guide_20-07
EN
6
7
Loosen the screws holding the door struts (8 pcs.) and
remove them together with the door.
Loosen screws (2 pcs.) and remove the crossbar.
8
9
Unscrew the brackets at the corners that secure the rotor
housing to the top and bottom of the section (brackets may
not be used in smaller units).
Disconnect cable connections from the filters, inspection or
recirculation section side. Pull the rotor housing out of the
section about 10 cm. Pull the cable connections through
the gap between the rotor housing and the fan section and
disconnect them.