17
UAB KOMFOVENT we reserve the right to make changes without prior notice
VERSO PRO2_guide_20-07
• Efficiency
Heat exchanger parameters are displayed in real-time.
In this menu you can also calibrate CF heat exchanger
1
, if not calibrated during the first start-
up. If calibration was successful and the display shows “Calibrated”, there is no need to repeat it.
During calibration, the unit will run for 10 minutes by changing fan speed and will be measuring
pressure inside the unit, therefore, do not open the unit door, do not adjust the duct system or
change parameters at that time. To stop calibration, turn off the unit with a remote controller.
• Filter status
When replacing filters with filters from different manufacturers or
different filtration class, calibration of clean filters is recommended.
During calibration, the unit will operate at a maximum speed for a
few minutes, measure the pressure difference upstream and down-
stream the filter and automatically determine the filtration class.
• Detailed information
This menu item displays readings of all sensors installed in the unit as well as information on
operation of individual devices of the AHU and other detailed data.
4.6. Functions
In menu item “Functions” you can activate or alter all functions of the unit. Press the function
name or an arrow to display the function settings.
Functions
Settings
Overview
Menu
Functions
1 / 2
Air quality control
Operation on demand
Outdoor compensated
ventilation
Summer night cooling
Minimum tempera-
ture control
Functions
2 / 2
Override function
Humidity control
Recirculation contro
1st additional zone
control
2nd additional zone
control
Scheduling
Function status is indicated in a box next to the function name:
Blank box: function is disabled.
Blue box: function is working.
Grey box: function is activated but not working.
In the settings of each function you can activate the function and alter operating conditions.
1
Only in CF units.
Calibrated
CF exchanger calibration
Efficiency status
83%
Energy saving
90%
Energy recovery
4,1 kW
Heat exchanger efficiency
67%
Extract air filter impurity
53%
Filter status
Clean filters calibration
Outdoor air filter impurity
67%
Extract air filter impurity
53%
Filter status
Clean filters calibration
Outdoor air filter impurity
Start
calibration?
350 m
3
/h
1 / 3
21,9 °C
Extract temperature
22,1 °C
Outdoor temperature
16,6 °C
Water temperature
25,3 °C
Supply temperature
Supply flow
Detailed information