18
1057616-W2-J
7.
Make sure that the hot and cold supplies have
been connected to the correct inlets, and that
all connections are watertight.
8.
Refer to section:
‘Commissioning’
.
OPERATION
For adjustable temperature models adjustment of
the blend temperature from the preset maximum
to cold is achieved by clockwise rotation of the
temperature knob.
For locked temperature models no user adjustment
is intended.
Control of flow is via a separate outlet valve(s),
refer to section:
‘Specifications’
.
Adjustable Temperature Models Only
Hot
Cold
COMMISSIONING
Commissioning must be carried out in accordance
with these instructions, and must be conducted by
designated, qualified and competent personnel.
Exercising the Thermostat
Thermostatic mixing valves with wax thermostats
are inclined to lose their responsiveness if not
used. Valves which have been in storage, installed
but not commissioned, or simply not used for
some time should be exercised before setting the
maximum temperature or carrying out any tests.
A simple way to provide this exercise is:
(a)
Make sure that the hot and cold water
are available at the valve inlets, and the
outlet is open.
(b)
Move the temperature control rapidly from
cold to hot and back to cold several times,
pausing at each extreme.
Maximum Temperature
Note!
For Type 3 healthcare installations the
maximum blend temperature is determined by
the application, refer to the
'TMV3 Requirements
Manual'
.
The maximum blend temperature obtainable by
the user should be limited, to prevent accidental
selection of a temperature that is too hot.
All Rada thermostatic mixing valves are fully
performance tested and the maximum temperature
is preset to approximately 41°C (222 models -
44°C) under ideal installation conditions at the
factory.
Site conditions and personal preference may
dictate that the maximum temperature has to be
reset following installation.
This mixing valve is provided with two methods
of temperature setting, an adjustable temperature
control knob which allows the user to select the
blend temperature between ambient cold up
to a preset maximum, or if considered more
appropriate, a locked cap can be fitted, allowing
no user adjustment.