23
COMMISSIONING
Maximum Temperature Setting
Before using the shower the maximum temperature
must be checked to make sure that it is at a safe
level. It has been preset to approximately 41°C at
the factory but due to variations in site conditions
the maximum temperature may need adjustment.
Note!
Make sure that the hot water temperature
is at least 55°C and that there is sufficient supply.
For Type 2 installations the maximum blend
temperature is determined by the application,
refer to the TMV2 Requirements Manual.
1.
Turn on the mixer to the maximum temperature
and maximum flow (i.e. fully anticlockwise) and
allow the temperature to stabilise.
If the temperature is too hot or too cold adjust
as follows:
2.
Carefully remove the concealing cap from the
control knob.
3.
Loosen the control lever grubscrew with the
2.5 mm hexagonal key (supplied) and pull off
the control lever.
4.
If applicable unscrew the hub retaining screw
with a 2.5 mm hexagonal key.
Note!
Do not remove the
hub.