TP-6833 2/16
46 Section 4 Communication and Accessory Connections
4.4
Load Shed
(Forced Transfer to OFF)
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Servicing the transfer switch. Hazardous voltage can
cause severe injury or death.
Deenergize all power sources
before servicing. Turn off the main circuit breakers of all
transfer switch power sources and disable all generator sets
as follows: (1) Press the generator set off/reset button to shut
down the generator set. (2) Disconnect power to all battery
chargers. (3) Disconnect all battery cables, negative (--) leads
first. Reconnect negative (--) leads last when reconnecting the
battery cables after servicing. Follow these precautions to
prevent the starting of generator sets by an automatic transfer
switch, remote start/stop switch, or engine start command
from a remote computer. Before servicing any components
inside the enclosure: (1) Remove all jewelry. (2) Stand on a
dry, approved electrically insulated mat. (3) Test circuits with a
voltmeter to verify that they are deenergized.
The load shed (forced transfer to OFF) accessory must
be factory-installed.
The load shed accessory is
available only on programmed-transition transfer
switches. See Figure 4-22 for an illustration of the load
shed acessory.
The load shed function requires an external signal
(contact closure) to initiate transfer to the OFF position.
Connect the external contact to input #1 (if available) or
input #2 on connector TB1 on the main logic board. See
Figure 4-23. Use #12--24 AWG wire and tighten to
0.5 Nm (4.4 in. lb.).
Use the Input/Output setup menu or Kohler SiteTech
software to assign the connected input (Main Board
Input #1 or #2) to the forced transfer to off function. If the
external contact is connected to a different input
connection on an optional I/O module, assign the forced
transfer to off function to that input.
GM23469
Figure 4-22
Load Shed Accessory (for
identification)