TP-6833 2/16
19
Section 2 Installation
Transfer Switch Position
Interlocked Weights
Maintenance Handle
Shaft Indicators
Normal
E
N
Lobe
Lobe
Weight
Weight
Hub
Hub
Up
E : O
upper contacts open
N : C
lower contacts closed
Up
Load
Disconnected
E
N
Up
E : O
upper contacts open
N : O
lower contacts open
Down
Emergency
E
N
Down
E : C
upper contacts closed
N : O
lower contacts open
Down
Note:
If Normal and Emergency connections are reversed this operation is also reversed.
Note:
The lobes prevent closing both N and E contacts at the same time.
Figure 2-12
Maintenance Handle Positions, 800--1200 Amp Model KCP Only.
ALL POWER MUST BE OFF !