TP-6196 5/04
56
Section 5 Component Testing and Adjustment
Fuel Conversion Procedure
Use the following procedure to convert from natural gas
to LP vapor.
See Figure 5-22 for the fuel system
component locations.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
the
generator
set.
Remove the negative (--) lead first
when
disconnecting
the
battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set.
Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
1. Place the generator set master switch in the OFF
position.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting in the fuel block. See Figure 5-21.
6. Remove the hose fitting from the natural gas outlet
port in the fuel block. See Figure 5-21.
7. Remove the plug from the LP port in the fuel block.
See Figure 5-21. Clean the plug with a dry cloth or
brush, apply fresh pipe sealant, and install the plug
into the natural gas outlet port.
8. Clean the hose fitting with a dry cloth or brush,
apply fresh pipe sealant to the threads, and install
the fitting into the LP port.
Note:
Do not adjust the fuel metering valves.
9. Slide the hose onto the hose fitting and secure it
with the clamp.
10. For the 12RES only:
Connect the digital
spark-advance module (DSAM) leads together for
natural gas. (Disconnect the leads for LP.) See
Figure 5-23.
11. Connect and turn on the new fuel supply.
12. Check that the generator set master switch is in the
OFF position.
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Start the generator set by moving the generator set
master switch to the RUN position.
16. Check for leaks using a gas leak detector.
17. Move the generator set master switch to the AUTO
position.
To convert from LP vapor to natural gas, follow the same
fuel conversion procedure, moving the hose fitting to the
natural gas port and plugging the LP port.
For the
12RES model, disconnect the DSAM leads for LP vapor.
See Figure 5-23.
2
GM29253
1. DSAM connector location
2. Fuel block
3. Fuel inlet, 1/2 in. NPT female
4. DSAM
3
1
4
Figure 5-22
Generator Set Fuel System Location, Air
Inlet Side