Section 3 Troubleshooting
Troubleshooting Chart, continued
Problem
Reference
Corrective Action
Possible Cause
Lacks
power
Air intake restriction, inadequate
cooling
Inspect air intakes and exhaust for obstructions.
Check air cleaner.
Section 2.5
Section 2.4
Generator overloaded
Reduce load.
Section 1.2
Spark plug(s)
Replace and regap plug(s).
Section 2.3
Spark plug wire(s)
Replace spark plug wires.
Engine S/M
DSAM leads incorrectly
connected or disconnected
(12RES only)
Connect for natural gas. Disconnect for LP.
Section 5.10.5
Insufficient fuel pressure
Check fuel pressure at carburetor outlet.
Section 5.10
Fuel line restriction
Check fuel pipe size.
Section 5.10
Fuel regulator
Check function of fuel regulator.
Section 5.10
Engine not running at rated rpm
Check controller settings for unit configuration (UC) and
engine type (EC).
Adjust governor speed.
Section 4.5
Engine power loss
Refer to the Engine Service Manual for troubleshooting
and repair instructions.
Engine S/M
Governor malfunction or
misadjustment
Test/readjust governor.
Section 5.8
Ignition system
Test and/or replace.
Engine S/M
Overheats
Inadequate cooling
Inspect cooling system for air intake obstructions.
Section 2.5
Fuel mixture adjustment incorrect Readjust fuel mixture.
Note:
Adjusting the fuel mixture may void the emission
certification.
Section 5.10
Low output
Generator overloaded
Reduce load.
Section 1.2
p
or
excessive
drop in
Incorrect controller configuration
Check and adjust the controller configuration
parameters.
Section 4.5
drop in
voltage
Incorrect controller voltage
settings
Check and adjust the controller voltage settings.
Section 4.5.3
Alternator or control system
Perform separate excitation procedure to isolate
problem to the alternator or the control system.
Section 5.2
SCR module
Check wiring and connections to the SCR module.
Check auxiliary winding fuse F1 (lead 55).
Replace SCR module and test voltage.
Section 5.11
Section 4.9
Controller
Check controller settings. Check controller fuse, wiring
and connections.
Before replacing controller, replace SCR module and
test voltage.
Section 4.5
Section 4.10
Rotor (open, grounded, or
shorted windings)
Test and/or replace.
Section 5.4
Stator (open, grounded, or
shorted windings)
Test and/or replace.
Section 5.3
Brush connection
Check for loose brush connections.
Check the resistance through the brushes. Resistance
through the brushes should be low, 0.1--0.2 ohms
without meter lead resistance.
Section
Low engine speed causing
voltage roll-off
Check system voltage/frequency (Uu) and engine type
(Ec) parameters
Adjust engine governor speed
Troubleshoot engine
Section 4.5.2
Section 4.5.3
Engine S/M
Light
flicker
Voltage stability (gain) setting
Check and adjust the voltage stability (gain) setting
using the ADC 2100.
Section 4.5.3